Unscrew the gas valve's outlet pressure
3.
test point 4.1 in Fig. 6.48 and connect a
pressure gauge.
Loosen the screws D and remove the
4.
service panel (Fig. 6.50).
Fig. 6.50
Turn on the boiler by means of the fused
5.
spur isolation switch provided with the
appliance.
6. Check that the boiler lights up uniformly
and adjust the flame height , if necessary.
To adjust the ignition gas pressure, set dip-
switch "3" (Fig. 6.51) to the "OFF" position
and adjust potentiometer marked "ACC" with
a screwdriver until correct ignition gas
pressure is obtained.
Refer to the table gas pressures at the burner
in the sections 4.5 or 4.6 for appropriate
value.
7. Having finished this procedure, reset dip-
switch "3" to the ON position.
56
Fig. 6.49
Poluzować punkt kontrolny ciśnienia na
3.
wylocie zaworu gazowego 36 (rys 6.5) i
podłączyć manometr.
Zluzować śruby D i zdemontować panel
4.
obsługi (rys 6.7)
Włączyć
5.
bezpiecznikowego wyłącznika zasilania
dostarczonego z urządzeniem.
Sprawdzić
6.
równomiernie
wyregulować wysokość płomienia.
Aby wyregulować ciśnienie zapłonu gazu,
ustawić mikroprzełącznik "3" (rys. 6.8) w
położenie OFF i wyregulować ustawienie
potencjometru z oznaczeniem "ACC" przy
pomocy śrubokrętu do momentu uzyskania
prawidłowego ciśnienia zapłonu gazu
Zapoznać się z właściwymi wartościami
ciśnienia gazu w palniku podanymi w tabeli w
pkt 4.5 lub 4.6.
Po zakończeniu tej czynności, ustawić
7.
ponownie
położenie ON.
Fig. 6.51
kocioł
za
czy
kocioł
zapala
i
w
razie
mikroprzełącznik
pomocą
się
potrzeby,
"3"
w