Output with thermostat cocks shut off
The boiler is fitted with an automatic by-pass
valve (4.1 on page 22), which protects the
primary heat exchanger.
In case of excessive reduction or total
blockage of water circulation in the central
heating system owing to closure of the
thermostatic valves or system component
cocks, the by-pass valve ensures a minimum
flow of water through the primary heat
exchanger.
4.8. Expansion vessel
The height difference between the pressure
relief valve and the highest point in the
system may be 7m at most.
For greater differences, increase the pre-load
pressure in the expansion vessel (4.1 on
page 22) and the system, when cold, by 0,1
bar for each additional 1m.
Wyjście z zamkniętymi kurkami regulacji
termostatycznej
Kocioł wyposażony jest w automatyczny
zawór
obejściowy
stanowiący
zabezpieczenie
ciepła obiegu pierwotnego.
W
przypadku
nadmiernego
całkowitego zablokowania obiegu wody w
instalacji
centralnego
spowodowanego
termostatycznych
instalacji,
zawór
minimalny przepływ wody przez wymiennik
ciepła obiegu pierwotnego.
4.8. Naczynie rozprężne
Różnica
wysokości
bezpieczeństwa a najwyższym punktem w
instalacji może wynosić najwyżej 7m.
W
przypadku
większych
zwiększyć ciśnienie obciążenia wstępnego w
naczyniu rozprężnym (38 na stronie 13) i w
instalacji, po jej ostygnięciu, o 0.1 bar na
każdy dodatkowy 1m.
(39
na
stronie
wymiennika
ubytku
ogrzewania
zamknięciem
zaworów
lub
kurków
w
części
przelewowy
zapewnia
pomiędzy
zaworem
różnic,
należy
13),
lub
33

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Parva control m90.32sv

Table of Contents