E. Vent Diagrams
Fire Risk. Explosion Risk.
Do NOT pack insulation or other combustibles between ceiling fi restops.
• ALWAYS maintain specifi ed clearances around venting and fi restop systems.
Install wall shield and ceiling fi
Failure to keep insulation or other material away from vent pipe may cause fi re.
1. Top Vent - Horizontal Termination
One Elbow
Note:
Use SL Series
components only.
Figure 5.4
Two Elbows
Note:
Use SL Series
components only.
H
2
Figure 5.5
14
restops as specifi ed.
H
1
Hearth & Home Technologies • BE-32 • InD • 2099-985 Rev. C • 9/06
WARNING
V
1
H
1
V
Minimum
H
1
1
Elbow only
1.5 ft
1 ft.
305 mm
2 ft.
2 ft.
610 mm
4 ft.
3 ft.
914 mm
9 ft.
4 ft.
1.2 m
12 ft.
V
+ H
= 30 ft. (9.1 m) Maximum
1
1
NOTE: There MUST be a
25% reduction in total H
when using fl ex vent except
when using the simple up
and out installation (see
Figure 5.3).
V
Minimum
H
+ H
1
1
6 in.
152 mm
1-1/2 ft.
1 ft.
305 mm
2 ft.
2 ft.
610 mm
4 ft.
3 ft.
914 mm
6 ft.
4 ft.
1.2 m
8 ft.
5 ft.
1.5 m
10 ft.
V
+ H
+ H
= 50 ft. (15.2 m) Maximum
1
1
2
H
+ H
= 17 ft. (5.2 m) Maximum
1
2
NOTE: There MUST be a
25% reduction in total H
V
when using fl ex vent except
1
when using the simple up
and out installation (see
Figure 5.3).
Maximum
457 mm
610 mm
1.2 m
2.7 m
3.7 m
Minimum
2
457 mm
610 mm
1.2 m
1.8 m
2.4 m
3.0 m