Cycle Sequence; Softener Set-Up - Hellenbrand ProMate Series Owner's Manual

Hellenbrand promate series twin alt manual
Table of Contents

Advertisement

Anytime cycle sequence is modified, softener set-up will revert to
manufacturer setting and must be reprogrammed as desired.
Cycle Sequence instructions allows the operator to set the order of the
cycle. The Softener System Setup allows the operator to set how long
the cycles will last. The operator may choose up to 9 cycles in any order.
END must be used as the last cycle option. The SOFTENING cycle
should only be used in brine prefill applications to allow salt to dissolve.
The following is an example of how to set a valve so that when regeneration is initiated, BACKWASH occurs first, REGENERANT
DRAW DN occurs second, a second BACKWASH is programmed third (used in high iron applications), RINSE occurs fourth, and
FILL occurs fifth. Factory cycle sequence for downflow is FILL, SOFTENING, BACKWASH, REGENERANT DRAW DOWN and
RINSE. Factory cycle sequence for upflow is FILL, SOFTENING, REGENERANT DRAW UP, BACKWASH and RINSE.
STEP 1CS
VALVE TYPE
1.0 T
STEP 2CS
SET
AUX MAV OFF
TRIGGER
SET
AUX RECLAIM START
STEP4CS
30:00
MIN
SET
15
STEP 1CS – Press NEXT and  simultaneously until TYPE appears on screen and release.
Then press NEXT and  simultaneously again for 3 seconds and release. If screen in step 2CS
does not appear in 5 seconds the lock on the valve is activated.
STEP 2CS – Valve Type. Use the  or  to select from 1.0", 1.25", 1.50", 2.0L", 2.0" valve.
Twin Alternating is a 1.0 (T)" valve. Press NEXT to go to Step 3CS.
STEP 3CS – Use the  or  buttons to select one of the following:
STEP 3CS
• Reclaim – Allows brine reclaimation. Select Reclaim for 1 Reclaim Event, Reclaim 2x for 2
reclaim events and Reclaim 3x for 3 reclaim events – See instructions ON PAGE 16.
• Separate Source –Allows Auxiliary MAV to switch positions before the start of regeneration
and to switch back at the end of regeneration. See instructions in Step 6CS.
• Off - Factory Setting is Off
Press NEXT to go to Step 4CS when reclaim selected as trigger. Press REGEN to return to
previous step.
STEP 4CS – Only displays if reclamation of brine is enabled in Step 3CS. Use the  or 
buttons to select the number of minutes after the start of regeneration the MAV will divert the
brine waste water from the plumbing drain receptacle to the brine tank. Start of regeneration
is defined as any mode that is not fill or softening. Use Table 1 on page 16 for settings.
Press NEXT to go to Step 5CS. Press REGEN to return to previous step.

CYCle SeQuenCe

BACKWASH
Cycle Options
REGENERANT
DRAW-DN
RINSE
SOFTENING
REGENERANT
DRAW-UP
FILL
END