4.5.2.3

Daily Trend

This function gives access to the daily trend High and High-High alarm parameters:
• DailyTrend: Current reading of daily trend, in ppm/x days. Same value as the one shown
in the Main Display mode.
• DayTrAlr H: Set point of daily trend High alarm.
• DayTrAlr HH: Set point of daily trend High-High alarm.
• DayTrAlr Delay: Alarm delay for all daily trend alarms' set points, in % of the period.
• DailyTr Period (Extended Menu only): Period of the daily trend (number of days used
to calculate the gas level variation).
• DayTrAlr L (Extended Menu only): Set point of daily trend Low alarm.
• DayTrAlr LL (Extended Menu only): Set point of daily trend Low-Low alarm.
4.5.3

Temperature Submenu

The Temperature submenu allows the user to:
• Read the current temperature of the Hydran 201 sensor.
• Set the parameters of the sensor temperature alarm.
• Adjust the set point of the sensor temperature.
• Set the periods A and B.
• Read the actual set point, heating power and temperature of the heating plate.
Note: Temperatures displayed on the H201Ti's display are given in Celsius degrees.
For explanations on the H201Ti's heating system, see Section 2.6 on page 2-14.
The Temperature submenu gives access to the following parameters:
• SensorTemp: Current temperature of the H201 sensor.
• STempAlr LL: Low-Low alarm set point of H201 sensor temperature.
• STempAlr L: Low alarm set point of H201 sensor temperature.
• STempAlr H: High alarm set point of H201 sensor temperature.
• STempAlr HH: High-High alarm set point of H201 sensor temperature.
• TempoAlr Delay: Alarm delay for all above set points.
• Temp SetPoint (Extended Menu only): Set point of the H201 sensor temperature
(average target temperature).
Part 17997
Rev. 6, March 2011
Main and Extended Menus
4-17