Main Display Mode - GE Hydran 201 i Instruction Manual

Hide thumbs Also See for Hydran 201 i:
Table of Contents

Advertisement

Chapter 4 • Hydran 201Ti's Displays and Menus
The unacknowledged alarm messages are always displayed in priority. When an alarm
occurs, the Main Display mode is immediately replaced by the Unacknowledged Alarms
mode. If two or more unacknowledged alarms are present, the display scrolls through their
messages at the rate of one every five seconds.
The user acknowledges each alarm by pressing the ENTER key for each alarm message.
The flashing messages are then removed from the list one at a time. The H201Ti returns to
the Main Display mode when the user has acknowledged all alarms. Acknowledged alarms
that are still active are shown as non-flashing messages in the Main Display list (see
Section 4.2.2 on page 4-4). When an alarm condition disappears, this message is removed
from the Main Display list.
Almost all alarm messages are displayed as follows, whether the alarm is unacknowledged
(flashing) or not (alarm condition still present):
• The top line displays the alarm message (the name of the parameter that triggered the
alarm) followed by the alarm state: LL (Low-Low), L (Low), H (High) or HH
(High-High).
• The bottom line displays the parameter's alarm set point (not the measured value). The
LL, L, H and HH alarm set points can all be adjusted and turned off.
In this first example, the actual display is on the left and the comments are on the right:
Gas HH
300 PPM
4.2.2

Main Display Mode

When the H201Ti is operating properly (no unacknowledged alarms, keypad unused), the
messages shown in Table 4-1 on page 4-5 are displayed at the rate of one every five
seconds.
Note: The display shows the alarm setting that was exceeded, NOT the actual value of the
variable in alarm.
4-4
Gas High-High alarm
Gas level above 300 ppm
Rev. 6, March 2011
Part 17997

Advertisement

Table of Contents
loading

Table of Contents