6.4.11 Verifying and Setting the Operation Mode of the Alarm Relays
For details on the parameters and commands in the submenu Relays/Analog, see
Section 4.5.7 on page 4-23. For details on relays, see Section 10.2 on page 10-4.
1.
Access the submenu H201Ti V2.2x;Relays/Analog.
2.
Verify and set, as required, the three RelayMode parameters.
6.4.12 Verifying and Setting the Fail Alarm Conditions
1.
Access the submenu SysOK Relay;FaultTrig.
2.
Verify and set, as required, the 16 trigger conditions of the Hydran 201Ti's fail alarm
relay.
Note: An asterisk at the end of the display's bottom line indicates that the parameter is
turned on (the fail alarm is triggered if this condition is detected). A space indicates that
the parameter is off.
6.4.13 Verifying and Setting the Operation Mode of the Analog Output and
TDM Signal
1.
Access the submenu H201Ti V2.2x;Relays/Analog.
2.
Verify and set, as required, the parameters AnalogMode and TDM Mode.
6.4.14 Conclusion
If the configuration has been performed using a host computer connected to the DB-9
connector located at the back of the CPU module, proceed as follows:
1.
Access the submenu Communication.
2.
Set the parameter CommChannel (communication channel) to Supervisory Link.
3.
Press END to return to the Main Display mode.
The Hydran 201Ti configuration is now completed.
Part 17997
Rev. 6, March 2011
Configuring the Hydran 201Ti
6-35