Table D-9 - Sw1 Voltage Selector For The Hydran 201Ci-C - GE Hydran 201 i Instruction Manual

Hide thumbs Also See for Hydran 201 i:
Table of Contents

Advertisement

Terminal
Description
33
Cable shield
34
Not used
35
Serial data-, I/O
36
unit No. 1
Serial data+, I/O
37
unit No. 1
Loop supply-,
38
input
Loop supply+,
39
input
40
Cable shield
a.
Wires have a maximum section of 2.5 mm
b.
An isolating, double-pole breaker must be installed in accordance with IEC 947-1 and 947-3
standards.
Voltage Selector
115 V
230 V
a.
The voltage selector is factory-selected and configured as per user requirements.
Part 17997
From (internal)
Chassis
J15-3, supervisory
link connector No. 1 Isolated RS-485
J15-4, supervisory
link connector No. 1
J15-2, supervisory
link connector No. 1 Isolated +5 Vdc
J15-1, supervisory
link connector No. 1
Chassis

Table D-9 - SW1 Voltage Selector for the Hydran 201Ci-C

a
Voltage Range
90–132 Vac, 47–63 Hz
180–264 Vac, 47–63 Hz
Rev. 6, March 2011
Hydran 201Ci-C Communications Controller
To (external)
Supervisory link cable
shield of unit No. 2
transceiver
regulator input
Supervisory link cable
shield of unit No. 1
2
.
130-W maximum heating @ 264 Vac
Comments
Direct ground
connection
Must be
connected to
H201Ti
Isolated supply
built into
H201Ci
Direct ground
connection
Comment
D-7

Advertisement

Table of Contents
loading

Table of Contents