Installing The Hydran 201 Sensor; Figure 6-5 - Ensure Two Screw Holes Of The Adaptor Are Level - GE Hydran 201 i Instruction Manual

Hide thumbs Also See for Hydran 201 i:
Table of Contents

Advertisement

Chapter 6 • Hydran 201Ti Installation
2.
Screw the adaptor onto the valve and tighten it using a pipe wrench. Ensure two of
the screw holes of the adaptor (used to fasten the Hydran 201Ti's heating plate) are
level (horizontal); see Figure 6-5 on page 6-22.
The H201Ti can be installed either on a horizontal (recommended)
WARNING
CAUTION
or vertical valve. If installed vertically, read the points listed on
page 5-11.

Figure 6-5 - Ensure Two Screw Holes of the Adaptor Are Level

6.3.5

Installing the Hydran 201 Sensor

1.
Cover the sensor's threads with Teflon tape (see Figure 6-4 on page 6-21).
Use only Teflon tape to seal the threads of both the adaptor and
WARNING
CAUTION
H201 sensor. Wrap at least 4 to 5 layers of tape around the threads.
2.
Slightly loosen the sensor's bleed screw, using the supplied 5/32-in Allen key.
3.
Screw the sensor manually onto the adaptor.
4.
Tighten the sensor using General Electric Canada's Hydran 201TW tube wrench (see
Figure 5-4 on page 5-4) or a strap wrench. Do not use a pipe wrench. Do not use
excessive force when tightening the H201 sensor onto the valve.
Note: If the H201 sensor is installed horizontally, ensure the bleed screw is on top (at the
"12 o'clock" position); see Figure 6-6 on page 6-23.
6-22
Level
Rev. 6, March 2011
Part 17997