8.
Do not install the H201Ti on the inlet side of the radiator pump (see Figure 5-5 on
page 5-5).
Figure 5-5 - Do Not Install the H201Ti on the Inlet Side of the Radiator Pump
9.
Do not use galvanized fittings to install the brass adaptor and the sensor. Galvanized
fittings (pipes, reducing bushings, rings, etc.) may react with the oil and produce
elevated gas level readings. Similarly, do not use galvanized fittings on transformer
valves used for oil sampling.
Part 17997
Pump
outlet
Rev. 6, March 2011
Radiator
Pump
General Warnings
5-5