Cancelling The Fail Alarm; Cancelling The Gas Alarms - GE Hydran 201 i Instruction Manual

Hide thumbs Also See for Hydran 201 i:
Table of Contents

Advertisement

4.
Ensure:
• The System state indicator LED OK (item 25 in Figure 2-7 on page 2-12) is off.
• The NO contact of the fail alarm is open.
• The NC contact of the fail alarm is closed.
• If connected, the SCADA system has detected the alarm.
6.2.4.4

Cancelling the Fail Alarm

1.
Set the same parameter RelayMode to Normal.
2.
Ensure:
• The System state indicator LED OK (item 25 in Figure 2-7 on page 2-12) is lit.
• The NO contact of the fail alarm is closed.
• The NC contact of the fail alarm is open.
• If connected, the SCADA system has detected the state change of the fail alarm relay.
6.2.4.5

Cancelling the Gas Alarms

1.
Access the submenu Relays/Analog;GasH Relay.
2.
Set this relay's parameter RelayMode to Normal.
3.
Access the submenu Relays/Analog;GasHH Relay.
4.
Set this relay's parameter RelayMode to Normal.
5.
Ensure:
• The High alarm state LED H (item 27 in Figure 2-7 on page 2-12) is off.
• The High-High alarm state LED HH (item 26 in Figure 2-7 on page 2-12) is off.
• The System state indicator LED OK (item 25 in Figure 2-7 on page 2-12) is lit.
• The NO contact of the High alarm is open.
• The NC contact of the High alarm is closed.
• The NO contact of the High-High alarm is open.
• The NC contact of the High-High alarm is closed.
• The NO contact of the fail alarm is closed.
• The NC contact of the fail alarm is open.
Part 17997
Verification of Operation Prior to Installation