Clearances - Montigo L42DFN Installation & Maintenance Manual

L-series residential fireplace l42df indoor
Table of Contents

Advertisement

L42DF* Indoor Gas Fireplace
Fireplace without standard screen (pre-January 2015 manufacturing).
N.G. & L.P.
Top Vent
Ceiling
1" min.
12" max.
84"
Rear
Min.
Vent
REAR VENT
N.G ONLY
Fireplace with standard screen (post January 2015 manufacturing).
N.G. & L.P.
Top Vent
Ceiling
1" min.
12" max.
84"
Min.
Rear
Vent
REAR VENT
N.G ONLY
Figure 5. Combustible Framing for shelf over the fireplace, Top vent.

Clearances

1" clearance is maintained on sides and bottom of vent runs and 2"
above horizontal vent runs to any combustible material.
Page 8
Installation
Non-Combustible
materials. Alcove
over fireplace.
Min 1"
Non-combustible
header
3"
12"
door
opening
Floor
Non-Combustible
materials. Alcove
over fireplace.
Min 1"
Non-combustible
header
3"
10.5"
door
opening
Floor
L42DF*
10"
21"
† NOTE: Clearance from top of fireplace to a ceiling within the fireplace
enclosure.
When installing a shelf over the top of the fireplaces, the following
guidelines must be adhered to:
For Rear Vent applications, the minimum clearance is 2" from the rear of
the fireplace to a wall, or any combustible materials, and 10" clearance
from the top of the fireplace to the underside of any combustible shelf
materials.
For Top Vent applications, the minimum clearance is 2" from the rear
of the fireplace to a wall, or any combustible materials, and 21" to the
underside of any combustible shelf materials.
Installing The Standoffs
To avoid elevated mantel temperatures, all L42DF* gas
fireplaces are required to have the supplied standoffs installed.
The fireplace is supplied with two standoffs. Bend and install these
standoffs on top of the fireplace ensuring that the height of the standoff
maintains a 6" clearance.
Figure 7. Installing the standoff's.
Installing the Nailing Flange Extension
Once the fireplace is placed into the rough framed opening, the supplied
Nailing Flange Extension (Part No. L42087) must be fasten securely into
place, with nails or wood screws. as shown in Figure 8.
Figure 8. Installing the Nailing Flange Extension.
Note: The nailing flange extension can be substituted with a piece of
NON-Combustible material of the same size and thermal characteristics,
ie: cement board or equivalent. This is recommended in applications
where the facing materials will not adhere to the metal nailing flange.
2"
1"
0"
See Section 6
Finishing around
the fireplace
6"
6"
XG0181 - 150204