Way Valve Control - Panasonic CS-PW18DKE Service Manual

Table of Contents

Advertisement

(For 8.5.8 to 8.5.14 information applies only to Heating Operation)
8.5.8.
Restart Control (Time Delay Safety Control)
• When the thermo-off temperature (temperature which compressor stops to operate) is reached during:-
− Heating operation - the compressor stops for 3 minutes (minimum) before resume operation.
• If the operation is stopped by the remote control, the compressor will not turn on within 3 minutes from the moment operation
stop, although the unit is turn on again within the period.
• This phenomenon is to balance the pressure inside the refrigerant cycle.
8.5.9.
Compressor Reverse Rotation Protection Control
• If the compressor is operating continuously for 5 minutes or longer and the temperature difference between indoor heat
exchanger and intake air is 5°C or less for continuous 2 minutes, compressor will stop and restart automatically.
• Time Delay Safety Control is activated before the compressor restart.
L T = Indoor heat exchanger temperature - Intake air temperature
• This is to prevent compressor from rotate reversely when there is an instantaneous power failure.
8.5.10. Overload Protection Control
• Outdoor Fan Control
− If the temperature of the Outdoor Heat Exchanger less than -3°C, Outdoor Fan is ON. The Outdoor Fan stop, when Outdoor
Heat Exchanger temperature is T
The Outdoor Fan restarts when the indoor heat exchanger temperature falls to 49°C.
During starting of Heating mode and after deice, Outdoor Fan ON for 90 sec. (Hi).
• Compressor High Pressure Control
− If the indoor heat exchanger becomes 68°C or more, the compressor will stop and restart automatically.
− Time Delay Safety Control is activated before the compressor restart.

8.5.11. 4-Way Valve Control

• 4-way valve always on during Heating operation. (except deicing operation)
• When the unit is switched off by remote control during Heating operation, the 4-way valve stay at Heating position for 5 minutes.
• This is to prevent the refrigerant flow process sound for being occur.
or more according to Outdoor Air Temperature region as table below:
b
19
CS-PW18DKE CU-PW18DKE

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cu-pw18dke

Table of Contents