Field Wiring; Power Circuit, Safety Device, And Cable Requirements - Daikin RQYQ140PY1 Installation Manual

Vrv iii-q series
Hide thumbs Also See for RQYQ140PY1:
Table of Contents

Advertisement

7.

FIELD WIRING

CAUTION
• All field wiring and components must be installed by a licensed
electrician and must comply with relevant local and national reg-
ulations.
• Be sure to use a dedicated power circuit. Never use a power sup-
ply shared by another appliance.
• Never install a phase advancing capacitor. As this unit is equipped
with an inverter, installing a phase advancing capacitor will not only
deteriorate power factor improvement effect, but may also cause
abnormal heating of the capacitor due to high-frequency waves.
• Only proceed with wiring work after blocking off all power.
• Always ground wires in accordance with relevant local and
national regulations.
• This machine includes an inverter device. Connect earth and
leave charge to eliminate the impact on other devices by reducing
noise generated from the inverter device and to prevent leaked
current from being charged in the outer hull of the product.
• Do not connect the ground wire to gas pipes, sewage pipes, light-
ning rods, or telephone ground wires.
Gas pipes: can explode or catch fire if there is a gas leak.
Sewage pipes: no grounding effect is possible if hard plastic pip-
ing is used.
Telephone ground wires and lightning rods: dangerous when
struck by lightning due to abnormal rise in electrical potential in
the grounding.
• Be sure to install an earth leakage circuit breaker.
This unit uses an inverter, so install the earth leakage circuit
breaker that be capable of handling high harmonics in order to
prevent malfunctioning of the earth leakage circuit breaker itself.
• Earth leakage circuit breaker which are especially for protecting
ground-faults should be used in conjunction with main switch or
fuse for use with wiring.
Note
• Electrical wiring must be done in accordance with the wiring dia-
grams and the description herein.
• Do not operate until refrigerant piping work is completed.
(If operated before complete the piping work, the compressor may
be broken down.)
• Never remove thermistor, sensor or etc. when connecting power
wiring and transmission wiring.
(If operated with thermistor, sensor or etc. removed, the compres-
sor may be broken down.)
• This product have reversed phase protection detector that only
works when the power is turned on. If there exists black out or the
power is turned on and off which the product is operating, attach
a reversed phase protection circuit locally. Running the product in
reversed phase may break the compressor and other parts.
• Attach the power wire securely. Introducing power with a missing
N-phase or with a mistaken N-phase will break the unit.
• Never connect the power supply in reversed phase.
The unit can not operate normally in reversed phase.
If you connect in reversed phase, replace two of the three phases.
• Make sure the electrical unbalance ratio is no greater than 2%. If
it is larger than this, the unit's lifespan will be reduced.
If the ratio exceeds 4%, the unit will shut down and an malfunction
code will be displayed on the indoor remote controller.
• Connect the wire securely using designated wire and fix it with
attached clamp without applying external pressure on the termi-
nal parts (terminal for power wiring, terminal for transmission wir-
ing and earth terminal).
7-1 Power circuit, safety device, and cable
requirements
• A power circuit (see the following table) must be provided for con-
nection of the unit. This circuit must be protected with the required
safety devices, i.e. a main switch, a slow blow fuse on each phase
and an earth leakage circuit breaker.
• When using residual current operated circuit breakers, be sure to
use a high-speed type (1 second or less) 200mA rated residual
operating current.
• Use copper conductors only.
• Use insulated wire for the power cord.
• Select the power supply cable type and size in accordance with
relevant local and national regulations.
15
• Specifications for local wiring are in compliance with IEC60245.
• Use wire type H05VV when protected pipes are used.
Use wire type H07RN-F when protected pipes are not used.
Phase and
Voltage
frequency
φ 3, 50Hz
RQYQ140PY1
380-415V
φ 3, 50Hz
RQYQ180PY1
380-415V
RQCYQ280PY1
φ 3, 50Hz
380-415V
φ 3, 50Hz
RQCYQ360PY1
380-415V
φ 3, 50Hz
RQCYQ460PY1
380-415V
φ 3, 50Hz
RQCYQ500PY1
380-415V
φ 3, 50Hz
RQCYQ540PY1
380-415V
φ 3, 50Hz
RQCEQ280PY13
380-415V
φ 3, 50Hz
RQCEQ360PY13
380-415V
φ 3, 50Hz
RQCEQ460PY13
380-415V
φ 3, 50Hz
RQCEQ500PY13
380-415V
φ 3, 50Hz
RQCEQ540PY13
380-415V
φ 3, 50Hz
RQCEQ636PY13
380-415V
φ 3, 50Hz
RQCEQ712PY13
380-415V
φ 3, 50Hz
RQCEQ744PY13
380-415V
φ 3, 50Hz
RQCEQ816PY13
380-415V
φ 3, 50Hz
RQCEQ848PY13
380-415V
Note
The above table indicates power specifications for standard combi-
nations (see 2. INTRODUCTION).
Point for attention regarding quality of the public electric power
supply.
This equipment complies with respectively:
*(1)
• EN/IEC 61000-3-11
provided that the system impedance Z
is less than or equal to Z
max
*(2)
• EN/IEC 61000-3-12
provided that the short-circuit power S
greater than or equal to the minimum S
point between the user's supply and the public system. It is the
responsibility of the installer or user of the equipment to ensure,
by consultation with the distribution network operator if necessary,
that the equipment is connected only to a supply with respec-
tively:
*(1) European/International Technical Standard setting the limits
for voltage changes, voltage fluctuations and flicker in public
low-voltage supply systems for equipment with rated current
=75 A.
*(2) European/International Technical Standard setting the limits
for harmonic currents produced by equipment connected to
public low-voltage systems with input current >16 A and =75
A per phase.
• Z
less than or equal to Z
sys
max
• S
greater than or equal to the minimum S
sc
• Heat Pump series (RQ(C)YQ)
RQYQ140
RQYQ180
RQCYQ280=RQYQ140+RQYQ140
RQCYQ360=RQYQ180+RQYQ180
RQCYQ460=RQYQ140+RQYQ140+RQYQ180 No requirements 2993538
RQCYQ500=RQYQ140+RQYQ180+RQYQ180 No requirements 3266370
RQCYQ540=RQYQ180+RQYQ180+RQYQ180 No requirements 3539202
Recom-
Minimum
mended
circuit amp.
fuses
11.9A
15A
17.2A
20A
23.8A
30A
34.5A
40A
41.0A
50A
46.4A
60A
51.7A
60A
23.8A
30A
34.5A
40A
41.0A
50A
46.4A
60A
51.7A
60A
55.5A
70A
64.9A
80A
66.1A
80A
72.7A
90A
74.0A
90A
and
sc
value at the interface
sc
and
value.
sc
Minimum
Z
(Ω)
max
S
value
sc
No requirements
906902
No requirements 1179734
No requirements 1813804
No requirements 2359468