Hp 300 W Integrated Power Supply; Hp 750 W Cs -48 V Dc Power Supply (94% Efficiency) - HP ProLiant DL320e Gen8 v2 Maintenance And Service Manual

Hide thumbs Also See for ProLiant DL320e Gen8 v2:
Table of Contents

Advertisement

Rated input power
Power supply output
Efficiency
Maximum peak power

HP 300 W Integrated Power Supply

Specification
Input requirements
Rated input voltage
Rated input frequency
Rated input current
Rated input power
Power supply output
Efficiency
Maximum peak power

HP 750 W CS -48 V DC Power Supply (94% efficiency)

Specification
Input requirements
Rated input voltage
Rated input current
Rated input power (W)
Rated input power (Btus per
hour)
Power supply output
Rated steady-state power (W)
Maximum peak power (W)
CAUTION:
DC supply circuit to the earthing conductor at the equipment.
If this connection is made, all of the following must be met:
This equipment must be connected directly to the DC supply system earthing electrode
conductor or to a bonding jumper from an earthing terminal bar or bus to which the DC supply
system earthing electrode conductor is connected.
312 W; 1,066 Btu/hr
80%
250 W
Value
100 V AC to 127 V AC
200 V AC to 240 V AC
50 Hz–60 Hz
6 A max at 100 V AC
3 A max at 200 V AC
600 W
80%
350 W (duration less 10 sec at 25°C)
Value
-36 V DC to -72 V DC
-48 V DC nominal input
23 A at -36 V DC input
17 A at -48 V DC input, nominal
input
11 A at -72 V DC input
815 W at -36 V DC input
805 W at -48 V DC input, nominal
input
795 W at -72 V DC input
2780 at -36 V DC input
2740 at -48 V DC input, nominal
input
2720 at -72 V DC input
750 W
750 W
This equipment is designed to permit the connection of the earthed conductor of the