Alarm Indicators*
Alarm Code
P1, P2, P3
HA
HA2
LA
LA2
* Please note: the temperature alarms (HA, HA2, LA and LA2) are disabled during the first 23
hours of operation after the cooling unit is plugged in and/or turned on.
Alarms
The control panel has an audible buzzer and an alarm
indicator light (Row 4) that turns on when an alarm is
triggered. In addition, the control panel will flash the following
codes when an alarm is triggered:
What it means
Probe Failure
The temperature inside
the cellar is too warm
(above 70°F for more
than 1 hour)
The condenser
temperature is too high
(above 125°F for 2
hours)
The temperature inside
the cellar is too cold
(below 45°F)
The temperature at the
condenser coils
(outside the cabinet)
has dropped below the
alarm temperature
setting
What to do
Call CellarPro at 877.726.8496
Check seals;
Check if door was left open;
Lower the ambient temperatures
Check for appropriate installation,
ventilation, ambient conditions and
cooling capacity (Chapter II)
Clean the condenser coils (see
"Maintenance" in Chapter IV);
Check for obstructions to the intake
and/or exhaust vents;
Check that the condenser fan is
operating
Raise the ambient temperature;
Raise the "Minimum Set Point"
Lower the alarm temperature
setting as follows:
1. Depress the "Set" and "Down"
button for three seconds until
the display reads "HY"
2. Depress the "Set" and "Down"
button for seven seconds until
"PR2" flashes on the display
3. Using the "Down" button, scroll
until the display reads "AL2"
4. Depress the "Set" button and
lower the alarm temperature
setting to your desired setting
-19-