I've had the cabinet for some time, and the cabinet door(s) are no longer sealing
properly against the cabinet.
You can check the door seals by placing a flashlight inside the cabinet and aiming it at the
door. Then, close the door. If there are any gaps and the light shines through, the door is
not sealing properly.
Another way to check the seals is by closing each door on a dollar bill around the perimeter
of each door. It should be difficult to slide the bill along the edge of the door without
pulling out the bill.
If the door(s) aren't sealing properly against the cabinet, do the following:
1. Make sure the cabinet is level and the doors are aligned (refer to Chapter V)
2. If there is a kink in the rubber gasket on the door, use a hair dryer for several minutes
and stretch the gasket into the proper shape. Then, close the doors for several hours to
allow the gasket to regain its proper shape.
The cooling unit runs constantly.
The cooling unit is designed to turn on when the air temperature in the cellar rises ABOVE
the Minimum Set Point + Temperature Differential, and turn off when the air temperature
falls below the Minimum Set Point. For example, if the Minimum Set Point is 58°F and the
Temperature Differential is 4°F, the cooling unit will turn above 62°F and turn off below
58°F.
When bottles are first loaded in the wine cabinet, the cooling unit will run continuously
(even up to a week) until the temperature inside the cellar falls below the Minimum Set
Point.
The cooling unit will cool a maximum of 30°F below the ambient temperature in the space
outside the condenser coils. In other words, when the ambient temperature in the space
outside the condenser coils is 90°F, the cooling unit can't cool below 60°F inside the cellar.
Hot weather conditions, insufficient ventilation and/or dirty condenser coils can all cause the
cooling unit to run continuously. To reduce cycle times,
1. Clean the condenser coils
2. Check the ambient temperature in the space outside the condenser coils while the
cooling unit is running, making sure that the difference between this temperature and
the Minimum Set Point is no more than 30°F.