Refrigeration Cycle Diagram - Toshiba RAS-24UFHP-E5 Service Manual

Under ceiling/console type
Table of Contents

Advertisement

5-1. RAS-18UFHP-E5 / RAS-18NAH-E
Cooling
0.39m
Heating
(Connecting pipe)
∅12.70 mm
0.39m
(Flexible pipe)
∅ 12.70 mm
O.D.:12.70 mm
Packed valve
(∅12.70)
Heating
Cooling
4-way valve
Heating Cooling Compressor
Cooling
Heating
50Hz
Standard
Heating
High temperature*1
Low temperature
Standard
Cooling
High temperature
Low temperature
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
*1 : During heating overload, the high temperature limit control operation is included.

5. REFRIGERATION CYCLE DIAGRAM

Multi blade fan
P
PH340X3C-4KT1
Accumulator
Condenser
Propeller fan
Outdoor unit
Standard
pressure P
(MPaG)
1.66
2.18 ~ 2.34
1.20
0.48
0.60
0.32
T
Indoor unit
Evaporator
Capillary tube
∅0.6x600l
Mark (
) means check points of Gas Leak
Surface temp. of heat
exchanger interchanging
pipe T (°C)
43
47 ~ 55
34.0
10.8
15.0
1.8
– 16 –
FILE NO. SVM-06006
0.49m
(Connecting pipe)
∅6.35 mm
O.D.:6.35 mm
Packed valve
(∅6.35)
Capillary tube
∅2.0x1400l
Refrigerant
R-22 1.53kg
Ambient temp.
conditions DB/WB
Fan speed
(°C)
(indoor)
Indoor
High
20/–
Low
27/–
High
20/–
High
27/19
High
32/23
Low
21/15
Outdoor
7/6
24/18
–10/–10
35/24
43/26
21/15