Toshiba RAS-24UFHP-E5 Service Manual page 58

Under ceiling/console type
Table of Contents

Advertisement

[19 outdoor TD sensor error]
Is TD sensor
connected properly?
YES
Is TD sensor resistance value
(50 kΩ at 25°C) normal?
YES
[1E Discharge temp. error]
Is protective controller
such as discharge
thermostat normal?
YES
Is charged amount
of refrigerant normal?
YES
Is overload relay normal?
NO
Is TD sensor resistance value
(50 kΩ at 25°C) normal?
YES
NO
NO
Indoor P.C. board is defective.
NO
Are wires connected to
connector properly?
NO
YES
NO
Outdoor P.C.board is defective.
– 57 –
FILE NO. SVM-06006
Connect connector
properly.
Replace TD sensor.
Replace P.C. board.
NO
Connect wires to
connector properly.
Check and modify charged
amount of refrigerant.
Unit operates normally.
Replace TD sensor.
Replace P.C. board.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents