(2) Insert the connective cable fully into the termi-
nal block and secure it by screw tightly.
(3) Secure the connective cable with the cord clamp.
(4) Tightening torque should be 1.2 N.m (12 kgf.cm)
3-1-2. Caution in Mounting the Front Panel
When the panel is removed and mounted again, fol-
low the step described below.
(1) After fastening two screws, be sure to hook the
inside clicks (1) and (2) of the front panel shown
in Fig. 3-7, right gap is left between the front panel
and the rear plate.
Note:
If cooling (dry) operation is made without push-
ing the air outlet, dew can be attached on the
front panel surface. In addition, a gap between
the front panel and the body will become wider,
spoiling the appearance.
Fig. 3-5
Fig. 3-7
(5) Fix the wiring cover, rear plate bushing and front
panel on the indoor unit.
3-1-3. Precautions for Refrigerant Piping
(1) Under-side connection with piping
(1) Cut out the knockout piece from the right below
of the rear plate with a knife, etc. Smooth the cut
edge.
(2) Set the drain hose in the inner part of the indoor
unit and connecting cable in lower part of it.
(3) Wind the tape round them.
– 9 –
Fig. 3-6
Fig. 3-8
Fig. 3-9