8-14. DRY Operation

(The remote controller's MODE button is set to the
DRY position.)
(1) In this mode, a microprocessor control lowers hu-
midity while maintaining a constant temperature.
(2) The microprocessor turns the compressor on and
off at regular intervals (4 to 6 minutes on and/or
off). During the compressor off, the airflow fan
will operate in the ultra low position.
(3) The compressor and airflow fan will operate in-
dependent of the temperature control, though the
pattern of operation depends on the relation be-
tween room temperature (T
ture (T
), as shown below:
S
Fig. 8-26
Note:
Operation is controlled at temperature above, independent on the position of the room temperature control.
) and set tempera-
A
Fig. 8-27
– 29 –
Table 8-3
Relation between room
temp. (T
) and
A
set temp. (T
)
S
T
> T
+ 2
A
S
T
+ 2 > T
> T
S
A
S
T
> T
S
A
The airflow fan will operate in the Low position,
independent of the position of the airflow setting
control.

8-15. AUTO Operation

(The remote controller's MODE button is set to the
AUTO position and AUTO display is lit.)
(1) One of the 3 modes, Cooling, Fan only and Heat-
ing is selected according to room temperature at
which operation is to start, as shown in Fig. 8-27.
The Fan mode will continue until room tempera-
ture reaches a level at which another mode is
selected.
8-15-1. Temporary Auto
When the TEMPORARY switch is set to AUTO., the
set temperature is fixed at 24°C and controlled in ac-
cordance with the chart shown in Fig. 8-27.
OFF
ON
period
period
a
b
4 min.
6 min.
5 min.
5 min.
6 min.
4 min.