1.

INDOOR UNIT INSTALLATION

1.1
Selecting installation site
When the conditions in the ceiling are exceeding
relative humidity of 80%, or when fresh air is inducted into the ceiling,
an additional insulation is required (minimum
polyethylene foam).
1)
Select an installation site where the following conditions are
fulfilled and that meets your customer's approval.
- Where optimum air distribution can be ensured.
- Where nothing blocks air passage.
- Where condensate water can be properly drained.
- Where the false ceiling is not noticeably on an incline.
- Where sufficient clearance for maintenance and service can be
ensured.
- Where there is no risk of flammable gas leaking.
- The equipment is not intended for use in a potentially explosive
atmosphere.
- Where piping between indoor and outdoor units is possible
within the allowable limit.(Refer to the installation manual of the
outdoor unit.)
- Keep indoor unit,outdoor unit,inter unit wiring and remote
controller wiring at least
radios.This is to prevent image interference and noise in those
electrical appliances.(Noise may be generated depending on
the conditions under which the electric wave is generated,even
if
is kept.)
3.28ft /1m
- When installing the wireless remote controller kit,the distance
between wireless remote controller and indoor unit might be
shorter if there are fluorescent lights
in the room.The indoor unit must be installed as far as possible
away from fluorescent lights.
2)
Ceiling height
Install this unit where the height of bottom panel is more than
8.2ft
/
2.5m
so that the user cannot easily touch.
3)
Use installation hooks for installation.Check whether the
ceiling is strong enough to support the weight of the indoor
unit.If there is a risk,reinforce the ceiling before installing
the unit.
Space required for installation see the figure below (
direction)
0
86 F
/
30 C
0.4in /10mm
3.28ft /1m
away from televisions and
that
are electrically started
0
and a
thickness,
1
2
DANGER
Do not install the unit in an area where flammable materials
are present due to risk of explosion resulting in serious
injury or death.
WARNING
If the basis underneath the unit is not strong enough to
support the weight of the unit, the unit could be fall out of
:air flow
place and cause serious injury.
7
39.4in /1000
2
1
39.4in /1000
Air inlet
Air outlet
39.4in /1000
2
39.4in /1000
Unit:
in/mm