Nameplate
The following illustration shows a typical generator set
nameplate. Copy the model, serial, and specification
numbers from the nameplate into the spaces provided in
the product information section on the inside front cover
of this manual. See the service views in Section 1.9 for
the nameplate location.
Emission Information
The Kohlerr Model SV620 engine used on the
8RESV/RESVL generator set is certified to operate
using natural gas or propane fuel.
The Kohlerr Model KT725 engine used on the
10RESV/RESVL and 12RESV/RESVL generator set is
certified to operate using natural gas or propane fuel.
The Emission Compliance Period referred to on the
Emission Control or Air Index label indicates the number
of operating hours for which the engine has been shown
to meet CARB or EPA emission requirements. Figure 3
provides the engine compliance period (in hours)
associated with the category descriptor, which may be
found on the certification label.
Emission Compliance Period
Category C
EPA
250 hours
Moderate
CARB
125 hours
Figure 3 Emission Compliance Period
10
Introduction
GM12070
Category B
Category A
500 hours
1000 hours
Intermediate
Extended
250 hours
500 hours
Refer to the certification label for engine displacement.
The exhaust emission control system for the SV620
engines (8RESV/RESVL) is EM for U.S. EPA,
California, and Europe.
The exhaust emission control system for the KT725
engine (10RESV/RESVL and 12RESV/RESVL) is EM
for U.S. EPA, California, and Europe.
Generator Set Application
Kohlerr Power Systems (KPS) ensures that all Kohlerr
generator sets are certified to applicable standards for
their intended application. It is the owner/operator's
responsibility to operate Kohlerr generator sets
exclusively according to the directions provided in the
accompanying operation manuals.
Kohlerr generator sets designated as Stationary
Standby, Emergency or Emergency Standby may only
be operated for emergency power generation and for
maintenance/testing. Emergency power generation is
limited to power production when electric power from a
local utility (or the normal power source, if the facility
runs on its own power production) is interrupted.
The US Clean Air Act explicitly prohibits using
Emergency Standby generators as a primary electric
power source regardless of whether a site is connected
to the electrical grid. Emergency Standby generators
may NOT be used to power sites which are not
connected to an electric utility. The U.S. Clean Air Act
authorizes owner/operator fines of up to $3,750 per day
of operation in violation of the generator set's
certification.
Owners/operators should familiarize themselves with
and perform all testing, maintenance, notification,
reporting and record keeping as required by the Clean
Air Act. In most cases, performance testing is not
required if the generator is operated and maintained
according
to
the
operation
owners/operators must retain maintenance records.
manual.