Auxiliary Device Current Draw Worksheet - Honeywell ADEMCO VISTA SERIES VISTA-21iP Installation And Setup Manual

Hide thumbs Also See for ADEMCO VISTA SERIES VISTA-21iP:
Table of Contents

Advertisement

Installation and Setup Guide

AUXILIARY DEVICE CURRENT DRAW WORKSHEET

DEVICE
6150 Fixed-Word Keypad
6160 Alpha Keypad
6150V Fixed-Word Display Voice Keypad
6160V Alpha Display Voice Keypad
6270 Touch Screen Keypad
5881/5882 RF Receiver
5883 Transceiver
4219 Zone Expander
4204 Relay Unit
4229 Zone Expander/Relay Unit
4286 Phone Module
*
(Current available from Aux. terminals = 600 mA max.) †
*If using hardwire devices such as PIRs, refer to the specifications for that particular unit's current draw.
** Values are for standby/alarm; alarm for keypads means armed with backlighting on and sounder on
†In UL installations, maximum current draw from the Auxiliary Output and the Alarm Output combined must not exceed 600 mA (500 mA max from Aux. Output).
‡Values are for relays OFF/relays ON.
CALIFORNIA STATE FIRE MARSHALL (CSFM) AND UL RESIDENTIAL FIRE
The California State Fire Marshal and UL have regulations which require that all residential fire alarm control panels must be
provided with a backup battery which has sufficient capacity to operate the panel and its attached peripheral devices for 24 hours in the
intended standby condition, followed by at least 4 minutes in the intended fire alarm signaling condition. This control panel can meet
these requirements without using a supplementary power supply, provided that the panel's auxiliary power and bell output currents
are limited as indicated below.
OUTPUT LIMITATIONS AND CORRESPONDING REQUIRED BATTERIES
OUTPUT CURRENT LIMITATIONS
Output Current Total
600mA maximum total of
auxiliary power plus bell
output currents
‡ NOTE: Use two batteries, connected in parallel. Obtain an Ademco Battery Harness Kit SA5140-1. (Both batteries will fit inside the cabinet.)
2-2
CABINET
A
RECEIVER CIRCUIT BOARD
+
+
CONTROL
CIRCUIT
BOARD
INSTALLATION WITH RECEIVER CIRCUIT BOARD
WHITE
BLACK
MOUNTING
MOUNTING
CLIP
CLIP
NOTE
A COMBINATION OF THESE MOUNTING CLIPS HAS BEEN
INCLUDED IN YOUR INSTALLATION KIT.
USE THE APPROPRIATE CLIPS FOR MOUNTING.
IF NO RF RECEIVER IS USED, MOUNT THE PC BOARD USING
EITHER THE WHITE OR BLACK CLIPS, WHICHEVER ARE
INCLUDED IN THE CONTROL PANEL'S HARDWARE KIT.
Figure 3. Mounting the PC Board and RF Receiver
CURRENT
40mA/70mA**
40mA/150mA**
60mA/160mA**
60mA/190mA**
180mA/280mA**
60mA
80mA
30mA
15/180mA ‡
30/100mA ‡
300mA
24-HOUR BATTERY BACKUP REQUIREMENTS
Maximum Auxiliary Current
45mA
160mA
200mA
425mA
500mA
B
BOARD
SUPPORTING
SLOTS
CIRCUIT
BOARD
MOUNTING
CLIP
MOUNTING
CLIP
SUPPORTING SLOTS
GROUNDING
RED
MOUNTING
CLIP
ANTENNA AND GROUNDING
No. UNITS
TOTAL CURRENT
TOTAL =
BATTERY INFORMATION
Battery Capacity
Recommended Battery
To Use (Amp/Hrs)
4AH
NP4-12 (or ADEMCO 467)
7AH
8AH
14AH
17.2AH
CABINET
DETAIL A
SIDE VIEW
OF BOARD -
ANTENNA
(2)
SCREW
(2)
LUG
(2)
ANTENNA
MOUNT
(2 PLACES)
DETAIL B
LUG INSTALLATION
pc_mount-001-V1
(Yuasa Model No.)
NP7-12
NP4-12 (two) ‡
NP7-12 (two) ‡
NPG18-12