Keypad Notes

Optional VISTA-GSM4G
Module
Wire Run Chart For Devices* Drawing Aux Power From The Control (12V+ & 12V–)
Wire
TOTAL CURRENT DRAWN BY ALL DEVICES CONNECTED TO A SINGLE WIRE RUN
Size
50 mA or less
#22
900 ft (274m)
#20
1400 ft (427m)
#18
1500 ft (457m)
#16
1500 ft (457m)
*
Includes Keypads, RF Receivers, Zone Expander/Relay Units, and 4286 Phone Module.
Maximum wire lengths for any device that is homerun to the control can also be determined from the Wiring Run Chart, based on the current draw of that device
alone.
The length of all wire runs for both partitions combined must not exceed 1500 feet (457m) when unshielded quad conductor cable is used (750 feet if shielded
cable is used). This restriction is due to the capacitive effect on the data lines when quad cable is used.

Table of Device Addresses

This Device
RF Receiver
AUI 1
AUI 2
AUI 3
AUI 4
Internal IP/GSM Device
4286 Voice Module
Zone Expanders (4219/4229):
module 1 (for zones 09 - 16)
module 2 (for zones 17 - 24)
module 3 (for zones 25 - 32)
module 4 (for zones 33 - 40)
module 5 (for zones 41 - 48)
Relay Modules (4204):
module 1
module 2
module 3
module 4
Keypads:
keypad 1
keypad 2
keypad 3
keypad 4
keypad 5
keypad 6
keypad 7
keypad 8
RIS Communication
5800TM Module
** address 07 not available if zone-doubling enabled
†† Addressable devices are identified by "1" plus the device address when reporting. Enter a report code for zone 91 to enable addressable device reporting
(default = reports enabled). See field *199 for addressable device (ECP) 3-digit/2-digit identification keypad display options.
Set device addresses. Refer to the instructions included with the devices and set each
address according to the Table of Device Addresses.
See Keypad Programming Fields (fields *190-*196) in Section 4. Data Field
Programming for details on enabling keypad addresses, assigning keypad partitions
and selecting keypad sounding options.
IMPORTANT: Each keypad must be assigned a unique, predefined address, from 16 to
23. The first keypad is address 16 (default = partition 1, all sounds enabled).
TOUCH SCREEN KEYPAD (AUI) NOTES:
• • • • Use of up to four AUI devices (e.g., 6272, Symphony, 6280, Tuxedo) is independent
from standard keypads and does not affect the number of standard keypads the system
can support.
• • • • AUI devices must be set for address 1 or 2, or address 5 or 6 depending on which unit
is enabled in field *189.
• • • • To ensure proper AUI device operation, use AUI devices with the following rev levels:
6270 series use version 1.0.9 or higher; 8132/8142 (Symphony) series use version
1.1.175 or higher.
Refer to the VISTA-GSM4G Module Installation section later in this manual for
detailed explanation of its installation.
The module's address is internally set to 03 and cannot be changed.
100 mA
450 ft (137m)
700 ft (213m)
1100 ft (335m)
1500 ft (457m)
††
Uses Address Reports as
00
100
01
02
05
06
03
103
04
104
107
07**
08
108
09
109
10
110
11
111
12
112
13
113
14
114
15
115
16
n/a
n/a
17
18
n/a
19
n/a
20
n/a
21
n/a
22
n/a
23
n/a
25
n/a
28
n/a
300 mA
500 mA
150 ft (46m)
90 ft (27m)
240 ft (73m)
140 ft (43m)
350 ft (107m)
220 ft (67m)
550 ft (168m)
350 ft (107m)
Enabled By...
*56 zone programming: input device type entry
automatic if AUI enable field *189 enabled for AUI 1
automatic if AUI enable field *189 enabled for AUI 2
automatic if AUI enable field *189 enabled for AUI 1
automatic if AUI enable field *189 enabled for AUI 2
automatic if enabled in menu mode *29
automatic if phone module access code field *28 enabled
*56 zone programming: input device type, entry 2, then:
automatic if zone no. 9-16 set as AW type or relay assigned
automatic if zone no. 17-24 set as AW type or relay assigned
automatic if zone no. 25-32 set as AW type or relay assigned
automatic if zone no. 33-40 set as AW type or relay assigned
automatic if zone no. 41-48 set as AW type or relay assigned
*79 output device programming: device address prompt:
entered at device address prompt
entered at device address prompt
entered at device address prompt
entered at device address prompt
data field programming as listed below:
always enabled for partition 1, all sounds enabled.
data field *190
data field *191
data field *192
data field *193
data field *194
data field *195
data field *196
automatic
(used for Remote Interactive Services)
automatic
Programming Overview
600 mA
75 ft (23m)
120 ft (37m)
170 ft (52m)
270 ft (82m)
2-5