Download Print this page
LST SLR-E-IS Specifications

LST SLR-E-IS Specifications

Is optical smoke detector for hazardous areas

Advertisement

Quick Links

IS Optical Smoke Detector
SLR-E-IS for Hazardous Areas
• Conventional technology
• Optional connection of remote
indicator
• Extremely fl at design
• Function testable with test gas
• ATEX certifi ed
Description
The Intrinsically Safe Optical Smoke Detector SLR-E-IS
uses the scattered light principle and was developed
for the detection of smoke particles in explosion-prone
rooms. The modern design of the sensing chamber al-
lows to reliably evaluate the characteristics of fi re.
Conventional technology is used for alarm transmission
to the fi re detection control panel. In conjunction with the
Safety Barrier ES58-2, the detector reaches the given
Specifi cations
Ignition protection
Ex classifi cation
Current consumption at 24V
Ambient temperature
Relative humidity
Dimensions ø × H (incl. base)
Colour
Weight
Approval
Order number
Order name
Building Safety. Building Security.
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
Ex classifi cation. The two LEDs with 360° visibility indi-
cate the activated condition of the detector. By means
of an auxiliary module, the connection to an ADM loop
is possible.
A detector function test can be conducted by using test
gas. The detector is attached to the IS Detector Base
YBN-R/4IS.
intrinsically safe
EEx ia IIC T5
typ. 50µA (quiescent)
-10°C to +55°C
10 – 95% (no condensation)
100 × 46 (mm)
cream
115g
BAS01ATEX1281
LPCB 164a
241090
IS Optical Smoke Detector/Conv. SLR-E-IS
A
SLR-E-IS_DBL_LST_EN_0804.PDF • PAGE 1

Advertisement

loading
Need help?

Need help?

Do you have a question about the SLR-E-IS and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for LST SLR-E-IS

  • Page 1 • Function testable with test gas • ATEX certifi ed Description The Intrinsically Safe Optical Smoke Detector SLR-E-IS uses the scattered light principle and was developed for the detection of smoke particles in explosion-prone rooms. The modern design of the sensing chamber al- lows to reliably evaluate the characteristics of fi...
  • Page 2 Building Safety. Building Security. © LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27 OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED -10°C to +55°C (no condensation or icing) 10 – 95% (no condensation) 100 ×...