Download Print this page

LST HT-11003 Specification Sheet

Thermal ror detector

Advertisement

Quick Links

Thermal ROR Detector
HT-11003
• Addressable conventional technology
• Maximum temperature 75°C
• Individual detector addressing by
means of optional address module
• Optional connection of remote
indicator
• Extremely fl at design
• Sealed electronics
Description
The Thermal ROR Detector HT-11003 reacts to tempe-
rature changes within defi ned periods of time, up to a
maximum temperature of 75°C. The intelligent evaluati-
on of these data allows the early detection of spreading
fi res. The detector complies with Class BR and can be
used up to a room height of 6m.
Addressable conventional technology is used for alarm
transmission to the fi re detection control panel. By
Specifi cations
Operating voltage
Current consumption
Alarm temperature
Operating temperature
Ambient temperature
Relative humidity
Dimensions ø × H
Colour
Weight
Approval
Order number
Order name
Building Safety. Building Security.
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
means of the optional Address Module NG60-1, each
detector can be addressed individually, thus allowing to
display the detector address, as well as an assigned
element text, on a suitable fi re detection control panel.
A detector fault is indicated by a yellow fl ashing of the
multicoloured status LED.
The detector can be attached to various bases and it
can be protected against theft.
Supply through the detector line voltage
typ. 65µA (quiescent)
75°C (maximum-heat component)
max. +65°C
- 40°C to +80°C (no condensation or icing)
0 – 98% (no condensation)
100 × 36 (mm)
white
70g
VdS G204035
242032
Thermal ROR Detector/Conv./ORBIS/Apo HT-11003
A
HT-11003_DBL_LST_EN_0804.PDF • PAGE 1

Advertisement

loading
Need help?

Need help?

Do you have a question about the HT-11003 and is the answer not in the manual?

Questions and answers