Temperature Settings; Data Logging - Lochinvar FTxl 500 Service Manual

Table of Contents

Advertisement

1
Service
(continued)
Night Setback Override
Any Night Setback On trigger currently active or scheduled
within the next seven (7) days can be skipped. To skip a
trigger, go to the Night Setback Status Screen and press
the SKIP button. Rotate the NAVIGATION dial until the
arrow (>) is next to the trigger you wish to skip. Press the
NAVIGATION dial once. "SK" will appear next to that
trigger to indicate that it will be skipped. You can restore
an upcoming trigger by selecting that trigger, and pressing
the NAVIGATION dial again. The "SK" next to that trigger
will disappear.
To save any changes and return to the Home Screen, press
the RIGHT SELECT [HOME] key. To return to the Status
Screen without saving the changes, press the LEFT SELECT
[EXIT] key.
Display Timeout
This is the time in which the display remains illuminated.
The range is 10 seconds to 10 minutes. The default is 10
minutes.
Display Contrast
The contrast of the LCD display can be adjusted to improve
readability. The contrast is adjusted automatically when
the display board is tested at the factory, but different
ambient conditions may warrant changing the setting. This
parameter can be changed by accessing the Display Contrast
setting. The range of this parameter is -10 to +10. The
default setting is 0.

Temperature Settings

Space Heating (SH1, SH2, SH3) Set Point
Mixing valves are required for the
CAUTION
protection of any low temperature
loops.
There are three (3) individual user set points for better zone
control. These are listed as SH1 Set Point through SH3 Set
Point. If multiple set points are calling for heat the highest
set point has priority. The range is SH Minimum Set point
to SH Maximum Set point. The default is 125°F (52°C).
Space Heating (SH) Minimum Set Point
The SH minimum set point sets the minimum water
temperature set point that can be used for space heating
operation. The user or installer will not be able to program
the control with a lower SH set point. This parameter can
only be changed by the installer by accessing Minimum
SH Set point parameter. The temperature range of this
parameter is 32°F (0°C) to the space heating maximum set
point. The default value is 60°F (16°C).
Space Heating (SH) Maximum Set Point
The SH maximum set point sets the maximum water
temperature set point that can be used for space heating. The
user or installer will not be able to program the control with a
higher SH set point. This parameter can only be changed by
the installer by accessing Maximum SH Set point parameter.
The temperature range of this parameter is the space heating
minimum set point to 190°F (88°C). The default value is 185°F
(85°C).
SH1 - SH3 Offset Set Point
The SH offset sets how many degrees above set point the
temperature has to go before the boiler will shut off. This
parameter can only be changed by the installer by accessing
parameters SH1, 2 and 3 Offset Set point parameters. The
temperature range of these parameters is 0°F to 20°F. The
default value is 10°F.
SH1 - SH3 Differential Set Point
The SH differential sets how many degrees below the offset the
temperature has to drop before the boiler turns back on. This
parameter can only be changed by the installer by accessing the
SH1, 2 and 3 Differential Set point parameters. The range is 0°F
to 60°F. The default is 20°F.
3-Way Valve Time
The optional Lochinvar Multi-Temperature Loop Control
Board (MTLC) can be used to control the supply temperature
in up to three (3) sub-loops, corresponding to each of the three
(3) SH set points, through the use of 3-way mixing valves. To
ensure the MTLC will control these temperature properly, it is
necessary to let the control know how much time these mixing
valves require to fully open and close. Program this time into
the 3-Way Valve Time parameter. Since this parameter applies
to all of the mixing valves used, the actual open/close time
must be approximately the same for each one. The minimum
setting is 1 second, and the maximum setting is 255 seconds.
The default setting is 20 seconds.

Data Logging

Reset log errors
The reset log errors function clears the last 10 errors log.
Service Manual
21