GAYLORD Ultima Vent GX2-UV Technical Manual page 19

Non water-wash ventilators
Table of Contents

Advertisement

TERMINAL
TROUBLESHOOTING UV SYSTEM
L1
Main Power Connection : Hot
L2
Main Power Connection : Neutral
1
Output to Supply Fan Motor Starter
5
120 VAC Neutral Leg
8
Output to Exhaust Fan Motor Starter
FS1
Supply Fan Fire Switch Connections
FS2
N.C. Contacts
FS3
Exhaust Fan Fire Switch Connections
FS4
N.O. Contacts
1U
Input from "UV System On" (Green)
2U
Input from "UV Lamp Failure" (Amber)
Input from "UV Safety Interlock Activated"
3U
(Red)
5U
120 VAC Neutral Leg
6U
Output to UV Lamps Contactor
120 VAC - when UV lights should be on
0 VAC
- when UV lights should be off
(Refer to UV Status Light Chart on following page)
TROUBLESHOOTING
CUV-100 TERMINAL VOLTAGES
DESCRIPTION
19
FAN OFF FAN ON EXT. FIRE
120 VAC 120 VAC
120 VAC
Common
0 VAC
120 VAC
0 VAC
High Voltage Common
0 VAC
120 VAC
120 VAC
Closed
Closed
Open
Open
Open
Closed
0 VAC
*
0 VAC
*
0 VAC
*
High Voltage Common
0 VAC
120 VAC
120 VAC
*
*
*