Installation
Horizontal Termination with One 90° Elbow
•
If using a Snorkel Termination (14" or 36") add the snorkel height to the vertical height (snorkel
terminations are used primarily for basement installations).
•
The termination must fall within the shaded area shown in the chart. Use the indicated restrictor
position.
19' max (5.8m)
15 feet (4.5m)
10 feet (3m)
5 feet (1.5m)
0 feet
© Travis Industries
(for qualified installers only)
Restrictor Position # 5
Restrictor
Position # 1
NOTE:
Horizontal sections require a 1/4" (0.250mm)
rise every 12" (305mm) of travel.
NATURAL GAS: Min. 2' (0.61m) Section Required
PROPANE (LP): Min. 3' (0.915m) Section Required
4090717
NOTE:
Restrictor positions are based
upon lab tests. The ideal
restrictor position may vary
slightly, especially when the
termination is near a
demarkation line.
15
19' max (5.8m)
15 feet (4.5m)
10 feet (3m)
5 feet (1.5m)
0 feet
100-01225_000