Electrical Service
All wiring must conform to local, state and national
codes.
VOLTAGE
The maximum allowable voltage variation is ± 10% of
the rated voltage on the ice machine model/serial
number plate at compressor start-up.
FUSE/CIRCUIT BREAKER
A separate fuse/circuit breaker must be provided for
each ice machine. Circuit breakers must be H.A.C.R.
rated (does not apply in Canada).
The ice machine must be grounded in accordance
with national and local electrical codes.
GROUND FAULT INTERRUPTER CIRCUIT (GFIC)
A GFCI/GFI circuit protection is not recommended
with our equipment. If a GFCI/GFI is required by code
a GFCI/GFI breaker rather than outlet must be used to
avoid intermittent nuisance trips.