Ratings

Model Number
Note: Change "N" to
"L" for L.P. gas models.
Min
CBN045
23
CBN075
38
CBN090
45
CBN135
68
CBN180
90
CBN215
108
CBN260
130
Maximum allowed working pressure is located on the rating plate.
NOTICE
Notes:
1. The ratings are based on standard test procedures
prescribed by the United States Department of Energy.
2. Net I=B=R ratings are based on net installed radiation of
sufficient quantity for the requirements of the building and
nothing need be added for normal piping and pickup.
Ratings are based on a piping and pickup allowance of 1.15.
3. Use only the vent materials and methods specified in the
Installation and Service Manual.
4. The Solution is orificed for operation up to 2000 feet
altitude. The ap pli ance will be derated 4% per 1000 feet
above 2000 feet el e va tion.
installations above 2000 feet elevation.
5. Ratings have been confirmed by the Hydronics Institute,
Section of AHRI.
Solution Boiler
I=B=R Rating
Input
Gross
Output
MBH
MBH
(Note 4)
(Note 1,5)
Max
45
37
75
62
90
75
135
112
180
149
215
178
260
216
Consult the factory for
Installation & Service Manual
Other Specifications
Net
I=B=R
Ratings
Boiler Water
Water,
Content
MBH
Gallons
(Note 1,5)
32
0.87
54
0.91
65
0.91
97
0.95
130
0.99
155
1.02
188
1.06
Figure A High Altitude Label Location
Water
Gas
Connections
Connections
1 1/2"
1/2"
1 1/2"
1/2"
1 1/2"
1/2"
1 1/2"
1/2"
1 1/2"
3/4"
1 1/2"
3/4"
2"
3/4"
UNIT EQUIPPED FOR
HIGH ALTITUDE
UP TO 2000 FT.
Vent
Size
(Note 3)
4"
5"
5"
6"
7"
7"
8"
5