Outdoor Air Reset Option; Additional Temperature Controls - Lochinvar SOLUTION 260000 Installation & Service Manual

45,000 - 260,000 btu/hr
Table of Contents

Advertisement

5
Electrical connections

Outdoor Air Reset Option

For boilers ordered with the Outdoor Air Reset option, there
is an additional control (FIG. 5-5). There are three setting
knobs for Shutdown, Outdoor Air Max., and Ratio. There is
also a switch to turn the outdoor air shutdown feature On or
Off. An O.A. Sensor is also included.
(c)2002 L.C.
(c)2002 L.C.
55
50
60
CN7
CN7
45
65
CN8
CN8
VR3
40
70
W1
W1
SHUTDOWN
55
50
60
45
65
VR1
40
70
CN1
CN1
O.A. MAX.
160
160
200
200
8 8
140
140
7 7
220
220
6 6
120
120
240
240
DIFFERENTIAL
DIFFERENTIAL
OFF
OFF
SETPOINT
SETPOINT
Figure 5-5_Optional Outdoor Air Reset Control
Shutdown
The Shutdown knob specifies the outdoor air lockout
temperature at which the control would prevent the unit from
operating.
Outdoor Air Max (O.A. Max)
The O.A. Max knob allows a reset up to the maximum
outdoor air temperature specified by this knob setting. When
the outdoor air temperature is above the specified setting, the
unit will not function in the O.A. Reset Mode, but will
continue to run at the selected set point temperature.
Note that the set point knob will now indicate the "minimum"
boiler temperature. Target temperature is determined by the
ratio and outdoor air temperature below the O.A. Max
setting.
Ratio
The Ratio knob allows control over the reset ratio to be used
during Outdoor Air Reset. The allowable ratios are as low as
0.5:1 or as high as 1.5:1.
Selecting the 0.5:1 ratio will increase the set point 0.5° for
every 1.0° drop in outdoor air temperature up to the
maximum set point temperature.
Selecting the 1.5:1 ratio will increase the set point 1.5° for
every 1.0° drop in outdoor air temperature up to the
maximum set point temperature.
38
CN1
CN2
CN2
CN3
CN3
O.A. SENSOR
CN4
CN4
ENABLE
ON
SW1
DISABLE
CN5
CN5
O.A. SHUTDOWN
1.0
0.9
1.1
CN6
CN6
1.2
0.8
1.3
0.7
W3
1.4
0.6
VR2
0.5
1.5
W1
W2
RATIO
10
11
11
9 9
10
10
12
12
15
15
5 5
13
13
14
14
VR2
VR2
VR3
VR3
5 5
15
15
(F-)0
(F-)0
20
20
HIGH-FIRE
HIGH-FIRE
OFFSET
OFFSET
TST2314
TST2314
If the outdoor design and boiler design temperatures are known,
the Ratio setting can be calculated using the following formula:
Ratio = (boiler design temperature - operator set point)
(O.A. Max. setting - outdoor design temperature)
Note that the reset set point cannot exceed the maximum set
point of the boiler thermostat.
These settings are illustrated graphically in FIG. 5-6.
OJ1
OJ1
OJ2
OJ2
CN9
CN9
Figure 5-6_Outdoor Air Control Example Chart
Outdoor Air Shutdown Enable/Disable Switch
The Outdoor Air Shutdown Enable/Disable switch turns the
outdoor air shutdown feature On and Off. Disabling the
Outdoor Air Shutdown feature allows the unit to operate
regardless of the outdoor air temperature. This is needed for
indirect domestic hot water systems for example.

Additional Temperature Controls

High Water Temperature Limit Con trol
The appliance is supplied with a fixed setting, auto-reset high
water temperature limit control. The setting of this control
limits max i mum discharge water tem per a ture.
temperature exceeds the setting, the limit will break the con trol
circuit and shut down the appliance. The limit control will only
be reset after the water tem per a ture has cooled well below the
setting of the limit. The auto-reset high water temperature limit
control is mount ed in the outlet side of the front header.