12.3. Calculating the additional refrigerant charge

NOTICE
Piping length is the one way length of liquid piping.
The additional charging amounts relate to the refrigerant piping
length as in "Maximum total one-way piping length" of the table
in paragraph
"8.4. Allowable pipe length and height difference" on
. (E.g. twin: L1+L2+L3).
page 8
Over 30 m, please add refrigerant quantity according to
following table.
For future servicing, mark with a circle the selected amount on the
tables below
For pair system
Table 1: Additional charging of refrigerant <unit: kg>
Connected piping length is between
Model
30~40 m
RZQG71
0.5
RZQG100~140
0.5
RZQSG100~140
0.5
Connected piping length is between
Model
15~20 m
RZQG71
0.5
RZQG100~140
0.5
RZQSG100~140
0.5
For twin, triple, and double twin system
Please charge additional according to the following calculation.
(additional amount is R1+R2)
1.
G1: total length of Ø9.5 mm liquid piping
G2: total length of Ø6.4 mm liquid piping
2.a G1>30 m
calculate length over 30 m (=G1–30 m)
Based on this length decide R1, R2 in the table
2.b G1≤30 m and G1+G2>30 m
calculate total length over 30 m (=G1+G2–30 m)
Based on this decide R2 in the table, R1=0
3.
Total additional charge amount
R=R1+R2 (kg)
Table 2: Length <unit: m>, additional charging of refrigerant
<unit: kg>
Liquid
Model
piping
Ø
Main
9.5
RZQG71
Branch
6.4
Main
9.5
RZQG100~140
9.5
Branch
6.4
Main
9.5
RZQSG100~140
Branch
6.4
RZQG71~140L + RZQSG100~140L
Split system air conditioners
4P339538-1A – 2014.03
Standard liquid pipe size
40~50 m
50~60 m
60~75 m
1.0
1.0
1.5
2.0
1.0
Size up liquid pipe size
20~25 m
25~30 m
30~35 m
1.0
1.0
1.5
2.0
1.0
Length exceeding "Chargeless length"
0~5
5~10 10~15 15~20 20~30 30~45
0.5
1.0
0.3
0.6
0.5
1.0
1.5
0.5
1.0
1.5
0.3
0.6
0.9
0.5
1.0
0.3
0.6
Example 1
RZQG100 type
outdoor heat pump
1.
G1=L1=35 m
2.
Over 30 m
a G1–30=5 m
b G2=12 m
3.
Refrigerant charge amount=R=R1+R2=0.5+0.6=1.1 kg
Example 2
RZQG125 type
outdoor heat pump
1.
G1=L1=5 m
2.
Over 30 m
a G1=5 m
b (G1+G2)–30=(5+54)–30=29
3.
Refrigerant charge amount=R=R1+R2=0.0+0.9=0.9 kg
NOTICE: Systems with sized-up liquid pipe
Replace 30 m by 15 m in calculations above and use
the table below.
G1: total length of Ø12.7 mm liquid piping.
Model
RZQG71
RZQG100~140
RZQSG100~140
2.0
2.0
1.2
L2=7 (Ø6.4)
L1=35 (Ø9.5)
L3=5 (Ø6.4)
G2=L2+L3=7+5=12
 Ø9.5 R1=0.5 kg
 Ø6.4 R2=0.6 kg
L2=17 (Ø6.4)
L1=5 (Ø9.5)
L3=17 (Ø6.4)
L4=20 (Ø6.4)
G2=L2+L3+L4=17+17+20=54
 R1=0.0kg
 Ø6.4 R2=0.9 kg
Length exceeding
"Chargeless length"
Liquid piping
0~5
5~10
size-up
0.5
1.0
size-up
0.5
1.0
size-up
0.5
1.0
50 type
indoor
50 type
50 type
indoor
50 type
indoor
50 type
10~15
15~20
1.5
2.0
Installation manual
14

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents