Carrier 58CTW Installation, Start-Up, Operating And Service And Maintenance Instructions page 37

Variable ---speed, ecm induced ---combustion 2 ---stage deluxe 4 ---way multipoise gas furnace series 100
Hide thumbs Also See for 58CTW:
Table of Contents

Advertisement

SETUP
SWITCH
SW1-1
SW1-2
SW1-3
SW1-4
SW1-5
SW1-6
SW1-7 & SW1-
8
SW2-1
SW2-2
SW 2-6, 7, 8
SW 2-3, 4, 5
SW2
A/C (8 7 6)
CF (5 4 3)
MODEL SIZE
045-12 / 036045
DEF
070-16 / 048070
DEF
090-16 / 048090
DEF
*110-22 / 066110
DEF
*135-22 / 066135
DEF
1. Default A/C airflow when A/C switches (SW2-6, 7, 8) are in OFF position
2. Default continuous fan airflow when CF switches (SW2-3, 4, 5) are in OFF position
* Continuous fan (CF) airflow for 110 and 135 models is the same as 090-16 / 048090
NOTE: CF airflow will not be higher than the selected A/C airflow
Fig. 53 - - Airflow Selection (based on 350 CFM/TON) for A/C (SW2- -6, 7, 8) and *CF (SW2- -3, 4, 5)
Furnace Setup Switch Description
NORMAL
SWITCH NAME
POSITION
Status Code Recovery
OFF
Low Heat Only
(Adaptive Heat Mode
OFF
when SW1-2 is OFF)
Low Heat Rise
OFF
Adjustment
Comfort/Efficiency
ON
Adjustment
CFM per ton adjust
OFF
Component Self Test
OFF
Blower OFF delay
ON or OFF
Twinning
OFF
CFM per ton Adjust
OFF
AC (Cooling Airflow)
OFF
CF (Continuous Fan)
OFF
Fig. 52 - - Furnace Setup Switch Description
SW2
SW2
SW2
A/C (8 7 6)
A/C (8 7 6)
A/C (8 7 6)
CF (5 4 3)
CF (5 4 3)
CF (5 4 3)
525
700
875
2
525
700
875
2
525
700
875
2
700
875
1050
2
700
875
1050
2
37
DESCRIPTION OF USE
Turn ON to retrieve up to 7 stored status codes for troubleshooting
assistance when R thermostat lead is disconnected.
When SW1-2 is OFF allows two-stage operation with a single stage
thermostat. Turn ON when using two- stage thermostat to allow
Low Heat operation when R to W/W1 closes and High Heat
operation when R to W/W1 and W2 close.
Turn ON to increase Low Heat airflow by 18 percent. This
compensates for increased return air temperature caused with
bypass humidifier.
Turn ON to decrease low heat airflow by approximately 7 percent
and high heat by approximately 10 percent for maximum comfort
Turn ON for 400 CFM per ton, Turn OFF for 350 CFM per ton. See
also SW2.
Turn ON to initiate Component Self Test for troubleshooting
assistance when R thermostat lead is disconnected. Turn OFF
when Self Test is completed.
Blower Off Delay time – adjustable 90 seconds to 180 seconds.
See table in Adjustments section or refer to unit wiring diagram.
Allows for selection of furnace Main (OFF) or Secondary (ON) when
Twinned furnace setup is required. See kit instructions for further
directions on installation and setup.
Allows additional CFM per ton selections when used with SW 1-5
325 CFM per ton (nominal) when SW 2-2 ON and SW 1-5 OFF
350 CFM per ton (nominal) when SW 2-2 OFF and SW 1-5 OFF
370 CFM per ton (nominal) when SW2-2 ON and SW 1-5 ON
400 CFM per ton (nominal) when SW 2-2 OFF and SW 1-5 ON
See Air Delivery Tables for model specific CFM vs. static pressure
The AC setup switches select desired cooling or high stage cooling
(two stage units) airflow. See Cooling Air Delivery Tables for
specific switch settings.
The CF setup switches select desired Continuous Fan Airflow
The CF switch position is the low cooling airflow selection for two
stage cooling units.
The CFM values are shown in the Air Delivery Tables below for
SW 2 settings. SW 2-3, 4, 5 cannot be set for airflow higher than
SW 2-6, 7, 8. See Continuous Fan Air Flow Table for specific
switch settings.
SW2
SW2
A/C (8 7 6)
A/C (8 7 6)
A/C (8 7 6)
CF (5 4 3)
CF (5 4 3)
CF (5 4 3)
1050
1150
1150
1
1050
1225
1400
1050
1225
1400
1225
1400
1750
1225
1400
1750
A14312
SW2
SW2
A/C (8 7 6)
CF (5 4 3)
1175
1685
1
1750
1
1925
1
1925
1
A14313

Advertisement

Table of Contents
loading

This manual is also suitable for:

58cty