4.9.3

CONSOLE REPORT CODES

PURPOSE:
To view and edit the eight Console report codes. These codes are sent
for Console events such as the Console emergency button, inactivity
alarm, Console low battery and battery restore, no AC and AC restoral.
Activity On & Off reports occur when the Console's activity timer is turned
on or off. The cancel report occurs when the Console's CLEAR button
is pressed during an alarm. The Automatic Test Report occurs every 1,
7, or 30 days if the Automatic Test Report is enabled (see Section 4.8).
No AC and AC restoral reporting is not supported in Versions 1.0 to 1.4.
NOTE: These report codes are sent for both 4 by 2 General and
4 by 2 Point-by-Point Reporting.
USER RESPONSE:

CONSOLE REPORT CODES

!
Enter a new two-digit report code for any Console event that needs
to be changed.
NOTE: Entering a "0" for a report code will prevent that event from
reporting.