Download Print this page
wattstopper LMDC-100 Quick Start Guid

wattstopper LMDC-100 Quick Start Guid

Digital lighting management dual technology ceiling mount occupancy sensor

Advertisement

Quick Links

THIS UNIT IS PRE-SET FOR PLUG N' GO™
OPERATION, ADJUSTMENT IS OPTIONAL.
For full operational details, adjustment and more
features of the product, see the DLM System Installation
Guide supplied with the LMRC-102 and also available at
www.wattstopper.com
INSTALLATION SHALL BE
IN ACCORDANCE WITH ALL
APPLICABLE REGULATIONS,
LOCAL AND NEC CODES.
Intended for Listed Class 2 DLM
Devices.
For Class 2 DLM devices -
To be connected to a Class 2
power source only.
SENSOR PLACEMENT (10' MAX. HEIGHT)
Sensor
COVERAGE PATTERN
The LMDC-100 provides a 360° coverage pattern.The
coverage shown represents maximum coverage for
walking motion at a mounting height of 10 feet.
CONNECTIVITY
The illustrations below show examples of free-topology wiring. The LMDC-100 communicates to all other Digital Lighting
Management devices connected to the low voltage DLM Local Network, regardless of their position on the DLM Local Network.
Corner Mount
Ceiling Mount
Sensor
Sensor
DLM Local Network
Low Voltage
LMRJ Cables
Switch
Switch
Daylight Sensor
For Class 2 Device Wiring Only –
Do Not Reclassify and Install as
Class 1, or Power and Lighting
Wiring.
Wire connections shall be rated
suitable for the wire size (lead
and building wiring) employed.
25'
25'
Line
Voltage
Line/Hot
Neutral
Black wire
White wire
Loads
1
LMRC
102
2
Room
Controller
Yellow wire
Red wire
to Load B (2)
to Load A (1)
J-Boxes
LMDC-100
Digital Lighting Management
Dual Technology Ceiling Mount
Voltage: .....................................................................................24VDC
Current Consumption: ...............................................................20mA
Power Supply: ................... Watt Stopper/Legrand Room Controllers
Connection to the DLM Local Network ........................ 2 RJ-45 ports
DLM Local Network Characteristics:
Provides low voltage power over Cat 5e cable (LMRJ).
Supports up to 24 communicating devices, including 4
LMRC-10x or LMPL-101 max per each DLM Local Network
Free topology up to 1,000ft of low voltage cable.
Environment .......................................................For Indoor Use Only
Operating Temperature ................. 32° to 131°F (0° to 55°C)
Storage Temperature ....................23° to 176°F (-5° to 80°C)
Relative Humidity ........................ 5 to 95% (non condensing)
Patent Pending
Pendant
xture
Mount sensor at least 6' away from air supply.
Avoid obstacles that block sensor's line-of-sight.
PIR
Coverage
Ultrasonic
Coverage
25 ft x 25 ft
(7.62m x 7.62m)
Room
Controller
J Box
To
Load
Ceiling Mount
Occupancy
Sensor
Occupancy Sensor
Strong air
Sensor
supply
6'
25 ft
(7.62m)
Switch

Advertisement

loading

Summary of Contents for wattstopper LMDC-100

  • Page 1 (7.62m x 7.62m) CONNECTIVITY The illustrations below show examples of free-topology wiring. The LMDC-100 communicates to all other Digital Lighting Management devices connected to the low voltage DLM Local Network, regardless of their position on the DLM Local Network. Corner Mount...
  • Page 2 LEDs turn ON and OFF but 1. Make sure device is not in PnL. load doesn’t switch 2. Check load connections to room controller. 2800 De La Cruz Blvd. Phone: 800.879.8585 10/2014 Please Santa Clara, CA 95050 www.wattstopper.com 11434r2 Recycle...