LG AMNW07GDBL1 Service Manual page 90

Lg multi-inverter type air conditioner svc manual(general)
Hide thumbs Also See for AMNW07GDBL1:
Table of Contents

Advertisement

Display
Title
code
High temperature in
32
Discharge pipe of the
inverter compressor
WARNING
Before checking PCB or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby state
of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.
Copyright ©2014 LG Electronics. Inc. All right reserved.
Only for training and service purposes
Cause of error
• Overload operation
(Outdoor fan constraint,
screened, blocked)
• Refrigerant leakage
(insufficient)
• Poor INV Comp
Discharge sensor
• LEV connector displaced
/ poor LEV assembly
- 89 -
Part 5. Trouble Shooting
Check point & Normal condition
• Check outdoor fan constraint/ screened/ flow
structure
• Check refrigerant leakage
• Check if the sensor is normal
• Check the status of EEV assembly
CN_TH3
(RED 4Pin Connector)
LGE Internal Use Only

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents