LG AMNW07GDBL1 Service Manual page 80

Lg multi-inverter type air conditioner svc manual(general)
Hide thumbs Also See for AMNW07GDBL1:
Table of Contents

Advertisement

Display
Title
code
Max. C/T
22
WARNING
Before checking PCB or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby state
of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.
■ Error Diagnosis and Countermeasure Flow Chart
Is installation
condition normal?
Yes
Are the resistance
Between each phase and
insulation resistance of Inverter
compressor normal?
Yes
Is compressor
Wire connection
condition normal?
Yes
Is inverter PCB assembly
power connection normal?
Yes
Is input voltage normal?
Yes
Is inverter PCB assembly
normal?
Yes
Recheck power and installation condition
Copyright ©2014 LG Electronics. Inc. All right reserved.
Only for training and service purposes
Cause of error
Input Over Current(36k-
17A↑ 54k-29A↑)
1. Check Pipe clogging/distortion
2. Check Covering (Indoor/Outdoor Unit)
No
3. Check EEV connector assemble condition/normal
operation
4. Check refrigerant pressure
→ Reassemble or manage if abnormality found
1. Check resistance between each terminal of compressor
(0.438~0.628±7%)
No
2. Check insulation resistance between compressor
terminal and pipe (over 2MΩ)
→ Replace compressor if abnormality found
1. Check inverter PCB assembly U,V,W connector
connection condition
No
2. Check wire disconnection and wiring
3. Check compressor terminal connection condition
(bad contact)
→ Reassemble if abnormality found
Check connection between inverter PCB assembly and
No
bridge diode(misconnection, disconnection)
→ wiring again if abnormality found
No
Check
L~N phase is 230V 15%
→ Check connection condition and wiring if power is
abnormal
No
Check inverter PCB assembly IPM normality
→ Replace inverter PCB assembly
- 79 -
Part 5. Trouble Shooting
Check point & Normal condition
1. Malfunction of Compressor
2. Blocking of Pipe
3. Low Voltage Input
4. Refrigerant, Pipe length, Blocked...
LGE Internal Use Only