LG AMNW07GDBL1 Service Manual page 52

Lg multi-inverter type air conditioner svc manual(general)
Hide thumbs Also See for AMNW07GDBL1:
Table of Contents

Advertisement

Display
Title
code
Communication
03
Wired R/C
Wired R/C
12V
S
GND
12Vdc
V
Check the Volt.
Check Point
1. Check the wire connection. (Open / Short) → Repair the connection
2. Check the soldering state of connector. (Soldered poorly) → Repair or Change the PCB.
3. Check the volt. Of main PCB power source. (DC 12V) → Repair or Change the main PCB.
4. Check the installation of wired remote controller. (Noise interference) → Adjust the state of installation
Copyright ©2014 LG Electronics. Inc. All right reserved.
Only for training and service purposes
Cause of error
• Open / Short
• Wrong connection
Indoor Unit
12V
S
GND
12Vdc
V
Check the Volt.
Check point & Normal condition
• Connection of wire
• Main PCB Volt. DC12V
• Noise interference
CN-REMO
- 51 -
Part 5. Trouble Shooting
LGE Internal Use Only

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents