Specifi cations
Wall Thickness
The appliance vent is suitable for penetrating a combustible wall up to 14" (36cm) thick.
A non-combustible wall can be any thickness up to the maximum horizontal run of vent pipe allowed for the
particular installation—see Horizontal Termination Venting Confi gurations section.
Supply Gas
Heater engine 530XAN /XCN is used for Natural gas installations.
Heater engine 530XAP/XCP is used for Propane gas installations.
The supply pressure must be between the limits shown in the Ratings table on the previous page.
The supply connection is 3/8''NPT female.
The opening for the gas supply line is at the rear left corner of the appliance.
Controls
The unit is supplied standard with a battery operated, hand-held remote control and receiver which has the ability
to adjust the gas input of the unit between the pilot setting and the maximum input .The pilot light must be manually
lit at the valve and may be left on or turned off with each use to save energy. The remote control provides full
thermostatic or manual operation with the option of programming thermostat function between certain times of the
day. Manual operation of the valve is also possible should the batteries or remote control fail.
Electrical
The unit does not require an electrical power source unless fi tted with an optional circulating fan.

Dimensions, Clearance and Framing

The dimensions, clearances and framing vary with each applications and with the front trim installed. Refer to the
installation instructions of the front trim chosen for more information.