Ras-24Ufp-Ar4 / Ras-24Ua-Ar4 - Toshiba RAS-18UFHP-E4 Service Manual

Under ceiling/console type
Table of Contents

Advertisement

5-7. RAS-24UFP-AR4 / RAS-24UA-AR4

0.39m
(Connecting pipe)
∅15.88 mm
0.39m
(Flexible pipe)
∅15.88 mm
O.D.:15.88 mm
Packed valve
(∅15.88 )
Accumulator
Compressor
PH400X3CS-4KTS1
50Hz
Standard
Cooling
High temperature
Low temperature
* SASO Standard's condition
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
Multi blade fan
P
Condenser
Propeller fan
Outdoor unit
Standard
pressure P
(MPaG)
0.4
0.6
0.3
T
Indoor unit
Evaporator
Mark (
) means check points of Gas Leak
Surface temp. of heat
exchanger interchanging
pipe T (°C)
11.0
12.0
1.0
– 27 –
FILE NO. SVM-05015
0.49m
(Connecting pipe)
∅6.35 mm
O.D.:6.35 mm
Packed valve
(∅6.35)
Capillary tube
∅2.4x1400S
Dryer
Refrigerant
R-22 1.70kg
Ambient temp.
conditions DB/WB
Fan speed
(°C)
(indoor)
Indoor
High
27/19
High
32/23
Low
21/15
Outdoor
35/24
52/31*
21/15

Hide quick links: