Retest After Repair - Lincoln Electric RANGER 3PHASE SVM207-A Service Manual

Lincoln electric welder user manual
Hide thumbs Also See for RANGER 3PHASE SVM207-A:
Table of Contents

Advertisement

F-52
Retest a machine:
• If it is rejected under test for any reason that requires you to remove any mechanical part which could affect the
machine's electrical characteristics.
OR
• If you repair or replace any electrical components.
Mode
Low Idle
High Idle
Output Control
Maximum
Output Control
Maximum
Output Control
Maximum
230 Volt Receptacle
Open Circuit
Load Volts
Voltage
246 - 264
216 - 250
Slip Ring Volts
32.0 - 45.0 VDC
OUTPUT CONTROL set at MAXIMUM (position 10).
1
Output values of each receptacle can vary within the range shown but must be within 2 volts of each other.
2
TROUBLESHOOTING AND REPAIR

RETEST AFTER REPAIR

ENGINE OUTPUT
No Load RPM
2200-2400
3700-3750
WELDER DC OUTPUT
Range Switch
Open Circuit
Maximum
WELDER AC OUTPUT
Range Switch
Open Circuit
Maximum
WELDER CV OUTPUT
Range Switch
Open Circuit
Wire Feed CV
AUXILIARY POWER RECEPTACLE OUTPUT
Load Amps
34 - 41.5
FIELD AMPS AND VOLTS
RANGER® 3 PHASE
1
Load Volts
Volts
65 - 72
21 - 26.5
1
Load Volts
Volts
73 - 80
25 - 32
1
Load Volts
Volts
29 - 33
19 - 23
115 Volt Receptacle
Open Circuit
Voltage
123- 132
Field Amps
6.5 - 7.5 VDC
Load RPM
NA
3100-3750
Load Amps
205 - 240
Load Amps
225 - 275
Load Amps
200 - 220
1
2
Load Volts
Load Amps
115 - 130
17.5 - 21
F-52

Advertisement

Table of Contents
loading

Table of Contents