Minimum Clearance - Ferroli XIGNAL CE Technical Information Installation And Service Instructions

Wall mounted, room sealed, fan assisted, gas combination boiler, computerised and synthesized voice
Table of Contents

Advertisement

Terminal Position
Fig. 3
Minimum Clearance mm
Fig. 5
NOTES
If a side outlet flue is to be used, a clearance of 75 mm will be needed on the flue outlet side of the boiler.
*
**
Access to the front of the boiler must be available for maintenance (min. 600 mm).
Air supply
APPLIANCE
FLUE
SYSTEM
APPLIANCE
LOCATION
IN ROOM
AIR VENT
IN COMPARTMENT
OPEN TO ROOM
AIR VENT
IN COMPARTMENT
OPEN TO OUTSIDE
ROOM-SEALED
AIR VENT AREAS
NIL
HIGH LEVEL:
252 cm
2
LOW LEVEL:
252 cm
2
HIGH LEVEL:
126 cm
2
LOW LEVEL:
126 cm
2
Fig. 4
(38 in.
2
)
(38 in.
2
)
(19 in.
)
2
(19 in.
2
)
11