Check code
Outdoor 7-segment display
Main
remote
Check
Sub-code
controller
code
H14
H14
H15
H15
Location
AI-NET central
of
Description
control
detection
remote
controller
I/F
Compressor 2
case thermo
activation
I/F
TD2 sensor
miswiring
(incomplete
insertion)
System
Error detection
status
condition(s)
All stop
Compressor 2 case
thermo was
activated.
All stop
Air discharge
temperature of (TD2)
does not increase
despite compressor
2 being in operation.
86
Check items (locations)
• Check Compressor 2 case thermo
circuit.
(Connector, Wiring, Circuit board)
• Open and check the service valve.
(Gas side, Liquid side)
• Check the outdoor PMV clogging
(PMV1, 2).
• Check the SV42 circuit.
• Check the SV4 circuit (SV41 / 42
miswiring).
• Check the opening status of indoor
PMV.
• Check the four-way valve error.
• Check the refrigerant shortage.
• Check installation of TD2 sensor.
• Check connection of TD2 sensor connector
and wiring.
• Check resistance characteristics of TD2
sensor.
• Check for defect in outdoor P.C. board (I/F).