Before you begin trouble shooting please go over the check list below.
1.
Replace batteries to new ones.
2.
Make sure the glass protective film is removed prior to operating the fireplace.
3.
Confirm the switch on the valve is on. ( see figure 3A)
4.
Confirm the gas is on.
5.
Purge the gas line of air up to the valve using purge port. ( see figure 3B)
6.
Confirm the pressure of inlet/ supply. Using purge port. (see figure 3B)
a.
Inlet pressure for NG should be 7" W.C
b.
Inlet pressure for LPG should be 11" W.C
7.
Valve and receiver wires are properly connected and tight and interrupter block is tight (
see figure 3C)
8.
Confirm the manual pilot valve operator is in the on position (see figure 3A)
APPENDIX E
Before You Begin Trouble Shooting
3 |
A p p e n d i x E