Gas Connections - Optal Clear 40 Installation & Operation Manual

40 series; 70 series; 80 series; 110 series; 120 series; 130 series; 150 series; 170 series; 200 series
Table of Contents

Advertisement

INSTALLATION INSTRUCTIONS
Read these instructions carefully. Failure to follow
property damage, personal injury, or loss of life. The
product must be installed and operated according to
all codes and local regulations.
It is the appliance manufacturer's responsibility to de-
termine GV60'
Do not remove screws from the gas valve. Do not ad-
just and/or alter any components marked with tamper
indicating paint. Motor knob is not to be removed.
1. Turn OFF gas supply at the appliance service
valve before starting installation, and perform a
Gas Leak Test after the installation is complete.
2. Install the sediment trap (where required) in the
gas supply line to prevent contamination of the
3. Use only your hand to push in or turn the gas control
knobs. Never use tools. If a knob will not push in or
service technician. Force or attempted repair will
Location
Locate the combination gas valve where it is not ex-
posed to steam cleaning, high humidity, dripping water,
corrosive chemicals, dust or grease accumulation, or
excessive heat.
To assure proper operation, follow these guidelines:
▪ Locate combination gas valve in a well-ventilated area.
▪ Mount combination gas valve high enough to avoid
▪ Make sure the ambient temperature does not exceed
the ambient temperature ratings for each component.
GV60 standard version is suitable for indoor use only.
APPENDIX B

GAS CONNECTIONS

Fire or Explosion Hazard. Can cause property
damage, severe injury, or death. Do not bend tubing
at gas valve connection point after compression
leakage at the connection.
Use new, properly reamed pipe free from metal or
material chips. When tubing is used, assure that ends
are square, deburred and clean. All tubing bends
must be smooth and free of distortion.
When threads are tightened, the valve must be held at
the designated clamping points (see gure 10). Do not
apply pressure to top casting or plastic cover.
Figure 9: Sediment Trap (where required)
Figure 10: S=Clamp Areas, B=Mounting Points
5 / 65
FOR OEM USE ONLY
Sediment Trap
Sediment Trap
Sediment Trap
A p p e n d i x B