Address Setting Of Addressable Expanders; Printer Connection To Console Or 'Arm S2000 - bolid S2000M Maintenance Manual

Fire and alarm console
Hide thumbs Also See for S2000M:
Table of Contents

Advertisement

S2000M
with the help of personal computer and utility 'uprog.exe'. To connect devices to personal
computer RS-232 – RS-485 interface converter needed ('PI', 'PI-GR' or 'S2000-PI'). 'S2000M'
console can be used as interface converter, transmitted in program mode. Connection circuit of
devices in programming at personal computer with 'S2000M' using shown on Figure 5.

2.1.4 Address setting of addressable expanders

If 'S2000-KDL' controller used in the system with address devices connected to the 2-
wire addressable communication line each device unique address (address set) has to be set
Expanders 'S2000-AR1' and 'S2000-AR2' addresses can be set with the help of console or
'uprog.exe' program. It is strongly recommended to program extender's addresses before
mounting, because when address is programmed controlled extender circuits is used. Description
of the extender address changing with the help of console is shown in the item 2.2.4.3.
PC
RxD
2
2
RxD
TxD
3
3
TxD
GND
5
5
GND
COM
DB9F
(DB9M)
PC – personal computer,
S2000M – check and control console "S2000M",
1 – connection cable "S2000" to the personal computer
Figure 5

2.1.5 Printer connection to console or 'ARM S2000'

If console is used with printer, the last one has to be set for next parameters according
instruction:
Description
Interface type
Transmission type
Number bit
Parity check
Code page
Auto line feed
On the site www.bolid.ru one can download instruction for configuring 'S2000M'
consoles for working with printer Epson LX300+. Epson LX300 and Epson LX300+ printers
have built-in customizing instruction.
Printer is connected to 'S2000M' console with the help of Printer cable (see section 1.3).
Connection circuit is shown on the Figure 1.
1
'S2000' console connection circuit. It is configured by personal computer through
RS-232 interface. Also it is shown using it as RS-232 – RS-485 interface
Setting name in LX-300+
I/F mode
Baud rate
Parity
Character table
Auto line feed
XT1.3
brown
5
TxD
yellow
6
DTR
green
7
GND
converter.
MAINTENANCE GUIDE
S2000М
XT1.2
A
3
B
4
Value (in LX-300+)
Serial or Auto
1200 BPS
None
PC 866
Off
RS-485
To devices
19

Advertisement

Table of Contents
loading