FIRE AND ALARM CONSOLE
S2000M
Maintenance guide

Advertisement

Table of Contents
loading

Summary of Contents for bolid S2000M

  • Page 1 FIRE AND ALARM CONSOLE S2000M Maintenance guide...
  • Page 2: Table Of Contents

    FIRE AND ALARM CONSOLE TABLE OF CONTENTS Description of the product and its operability Purpose Specifications Delivery set Description the product and capabilities Maintenance Preparation the product 2.1.1 General information 2.1.2 Connection console and devices to RS-485 interface instructions 2.1.3 Setting device configuration parameters 2.1.4 Address setting of addressable expanders 2.1.5 Printer connection to console or ‘ARM S2000’...
  • Page 3 2.2.4.10 Console entering into programming mode 2.2.5 Reset settings to default values 2.2.6 Console version update STORAGE TRANSPORTATION CERTIFICATION INFORMATION INFORMATION ABOUT MANUFACTURER WARRANTY Appendix A ‘S2000M’ console dimensions Appendix B Zone status list Appendix С The list of messages being displayed...
  • Page 4: Description Of The Product And Its Operability

    1 Description of the product and its operability 1.1 Purpose 1.1.1 ‘S2000M’ fire and alarm console is designed to work as part of fire-alarm system. It checks device states and gathers information, logs system events, indicates alarms, controls arm, controls disarm, controls by automatics. Console joins connected to it devices in one system, providing interaction between each other.
  • Page 5: Specifications

    S2000M MAINTENANCE GUIDE 1.1.5 Console may logically group alarm loops in partitions. Partition is a set of alarm loop that is controlled as one unit. This gives next advantages: − Arm/disarm require fewer users actions take less time, and probability of operators mistake is decreased also.
  • Page 6 FIRE AND ALARM CONSOLE 1.2.4 Length of the RS-485 communication line is no more then 4000 m. 1.2.5 Length of the RS-232 communication line is no more then 20 m. 1.2.6 Values of created by console radio noise are fewer standards. 1.2.7 Console is stable to the electromagnetic noise.
  • Page 7 S2000M MAINTENANCE GUIDE addresses of devices and address expanders, set, change and remove user passwords, change own password, setup and change console configuration for work with the partitions and relay outputs at personal computer using program ‘pprog.exe’ ver. 2.04. This password has no device and partition control rights! Engineer password can has from 1 up 8 digits.
  • Page 8 FIRE AND ALARM CONSOLE Table 2 Indicator ‘ALARM’ (red) State Indication Norm SILENT ALARM Blink with frequency 2 HZ ALARM Blink with frequency 1 HZ INTRUSION ALARM Blink with frequency 4 HZ Table 3 Indicator ‘FIRE’ (red) State Indication Norm FIRE Blink with frequency 2 HZ ATTENTION...
  • Page 9 S2000M MAINTENANCE GUIDE Note - Alarm indication at LED indicator and sound annunciator is made only if option ‘ALARM SOUND’ is on. Default option setting is ‘on’. 1.2.22 Console allow user to control by relay outputs of signal-start ‘S2000-SP1’ blocks, and also by ‘Signal-20P’, ‘S2000-4’, ‘Signal-20’...
  • Page 10 FIRE AND ALARM CONSOLE Number Program name Program description ‘SIREN’ If ‘Fire alarm’ then blink given time (1,5 s ON, 0,5 s OFF); if ‘Attention’, then blink given time (0,5 s ON, 1,5 s OFF); if ‘Intrusion alarm’, then ON for a given time; else OFF output.
  • Page 11 S2000M MAINTENANCE GUIDE Number Program name Program description ‘Turn off for a given If at least one zone is in the state ‘Auxiliary alarm’, then time when auxiliary OFF for a given time; alarm’ else ON output. ‘Turn on when If at least one zone is disarmed, then ON;...
  • Page 12 FIRE AND ALARM CONSOLE Number Program name Program description "Turn on if launching ON if launching has been failed (in "Launch fault" state); failed" else OFF. "Turn on when ON in "Auto extinguishing" state; autoextinguishing is on" else OFF. "Turn off when OFF in "Auto extinguishing"...
  • Page 13 9) Programs № 38-45 can be used in gas, powder or aerosol fire extinguishing systems based on “S2000M-ASPT” devices. These programs allow turning on or off device outputs both for given time or as long as on/off condition is in effect. Controlling without time restrictions is realized by givening the maximum control time value being egual to 8191,875 seconds.
  • Page 14: Delivery Set

    1.3 Delivery set 1.3.1 List of delivery set components of the console “S20000M” is shown in table 8. Table 8 Delivery set of console ‘S2000M’ Name Quantity Note Check and control fire-alarm ‘S2000M’...
  • Page 15: Maintenance

    Power supply – DC power supply from 10,2 to 28,4 V current supply no more than 150 мА. Figure 1 Typical maintenance connection ‘S2000M’ console circuit Attention! On the console board there is 5-pin auxiliary slot. It is prohibited to set pin tampers or shortly connect the pins if console power is on.
  • Page 16: Connection Console And Devices To Rs-485 Interface Instructions

    KS’). At all other devices jumpers should be removed. ‘S2000M’ console can be set at any place in the RS-485 line. If it is first or last device in the line, then between contacts ‘A’ and ‘B’ matching resistor 620 Ohm need to be set. Branches in the line are not undesirable, because they increase reflection signal in the line.
  • Page 17 Figure 2 Device RS-485 interface connection circuit. Below 2000 m Below 2000 m Below 2000 m PKU – console "S2000M"; IP – power supplier; PKP – alarm panel; R – matching resistance 620 Ohm. P – interface repeater; Figure 3...
  • Page 18: Setting Device Configuration Parameters

    For example, if transmission equipment imports delay 3 ms, then ‘S2000M’ console receive reply from device more then 6 ms after request. Because console waits reply from device no more 5 ms, device will not be detected. To solve these problems few connection parameters made customizable.
  • Page 19: Address Setting Of Addressable Expanders

    Epson LX300+. Epson LX300 and Epson LX300+ printers have built-in customizing instruction. Printer is connected to ‘S2000M’ console with the help of Printer cable (see section 1.3). Connection circuit is shown on the Figure 1.
  • Page 20: Using The Console For "Arm Orion" Redundancy

    The first backup mode named ‘S2000 / PC’ is to make ‘ARM Orion’ monitors all devices and registers states of them with ‘S2000M’ console being aside. If the computer has failed the console automatically connect the devices and take over the control. When recovering the computer assume the control again.
  • Page 21 There are two ways of switching the control from PC to the console: 1) by means of self- acting mechanically RS-485 lines switching with the help of “S2000M-SP1” relay units and 2) using the special console operating mode, that is interface converter mode with automatic transit to redundant mode.
  • Page 22 “S2000M-SP1” relay unit. The monitoring and controlling are carried out from the computer. The console is directly...
  • Page 23 2048 alarm loops and 511 partitions. It is possible to reserve the PC by several ‘S2000M’ consoles. One can connect only single console to the PC RS-232 interface therefore it is necessary to convert RS-232 interface to the RS-485 interface by means of ‘S2000-PI’...
  • Page 24 S2000М –‘S2000M’ alarm panel; S2000-PI – interface converter repeater "S2000-PI"; BP – power supply; 1 – connection cable "S2000-PI" and PC. Figure 7 Connection of several ‘S2000M’ to the PC with ‘ARM Orion’ with galvanic isolation of interface RS-485 diagram...
  • Page 25: Console Configuring

    To write or read the configuration ‘S2000M’ console has to be connected to personal computer. The console can be connected both via RS-232 or RS-485 interfaces. In the first case console is connected to computer as shown on the Figure 5, and the second case is shown on the Figure 8.
  • Page 26: Adding Devices Into Console Database And Partition Creation

    Adding devices into console database and partition creation Device loops can be included in partitions, and their outputs can be automatically controlled by ‘S2000M’ console, if these devices are presented in console database. To add the device specify it address and type.
  • Page 27: Setting Partition Control Rights And Password Programming

    2.1.7.3 Setting partition control rights and password programming Access to partition control functions is granted to users at password entering at ‘S2000M’ console, ‘S2000-K’ keyboards or ‘S2000-KS’, or at using Touch Memory key or Proximity card with ‘S2000-4’ or ‘S2000-2’, ‘Signal-20P SMD’ version 2.01 and above, ‘S2000-KDL’ version 1.15 and above.
  • Page 28 All partition control right information (access levels, password and device rights) are programming in the ‘S2000M’ console. Access levels and device rights can be given by program ‘ pprog.exe ’ only. Passwords can be set by both program ‘ pprog.exe ’, and by console.
  • Page 29: Setting Control By System Relay Outputs

    Key (card) code should be read and showed in ‘Code’ field. ‘S2000-KS’ or ‘S2000-K’ keyboard PIN-code should consisit from 4 digits. Such password can be programmed without ‘pprog.exe’, from console ‘S2000M’. Password programming is described in the item 2.2.4.5.
  • Page 30: Setting Message Transmission

    FIRE AND ALARM CONSOLE Attention! When output external control of ‘S2000-4’, ‘Signal-20P’ and ‘Signal-20’ version 02 devices is used internal control has to be removed, that is outputs have to be not connected to loops. If internal output control is used it is prohibited to use external control, that is outputs have to be not connected to partitions.
  • Page 31: Entry Zone Settings

    ‘S2000M’ panel with programmed partitions can be connected to ‘S2000-BI’ indication units. Prior, configuration of indication blocks with the help of ‘S2000M’ console or program ‘ uprog.exe ’ has to be set. Minimal setup is programming partition number for each indicator. At connecting indication units to ‘S2000M’...
  • Page 32: Using The Console For Creating Of Systems Controlling Gas, Powder Or Aerosol Fire Extinguishing Installations Based On "S2000-Aspt" Devices

    FIRE AND ALARM CONSOLE 2.1.7.9 Using the console for creating of systems controlling gas, powder or aerosol fire extinguishing installations based on "S2000-ASPT" devices The console is suitable in gas, powder or aerosol fire extinguishing systems based on "S2000-ASPT" devices especially in case of using several extinguishing areas at once. The console can be used in such systems as follows: 1) To indicate system status by means of "S2000-PТ"...
  • Page 33: Using The Console With Sprinkler Or Drencher Extinguishing Units Based On Devices

    S2000M MAINTENANCE GUIDE premises were opening). "AUTOMATIC MODE" indicator demonstrates the current launching mode (is auto launching mode on or not). "EXTINGUISHING" indicator demonstrates status of launching (that is no launching, launching delay, launching or launching failure). "S2000–PT" devices have some buttons for automatic mode controlling (turn on/off auto extinguishing mode) and for remote launching or canceling of auto extinguishing equipment launch.
  • Page 34: Console Mounting

    FIRE AND ALARM CONSOLE codes with corresponding authority levels are assigned in console configuration. Passwords being programmed into the console have some numbers transmitting by the console in arm and disarm messages as user’s identificators. 2.1.8 Console mounting Console can be mounted in any convenient place on the wall or on the other constructions protected from atmospheric condensation, mechanical damages and access of outliers.
  • Page 35: Displaying, Viewing And Printing Device Messages

    S2000M MAINTENANCE GUIDE 2.2.1 Displaying, viewing and printing device messages Console receives messages from device. They include event name, data (number and text partition description, device address, number of alarm loops, reader, relay, user identificator), and time. At LCD message indication in top line message name is displayed, and in bottom its source.
  • Page 36 ARMING’, ‘PART DISARMING’ include partition number and partition user. At printing address device and partition control reader number are printed also. Address in device message equal 0, if partitions controlled at ‘S2000M’ console. Display: ARMED PART Corridor 1-Floor - partition ‘ Corridor 1-floor ’ armed.
  • Page 37: Partition Arming And Disarming

    S2000M MAINTENANCE GUIDE LCD alarm message press keyboard button ‘CLR’. If all alarm messages are canceled, console will return in time displaying mode. The events below are shown in alarm level increasing order: − ‘Arm failed’; − troubles (‘Loop trbl short’, ‘Loop trbl open’, ‘Power failed’, ‘Battery failed’, ‘Zone config err’, ‘Fire trouble’;...
  • Page 38 FIRE AND ALARM CONSOLE ‘ERROR’ mode, display the message ‘ILLEGAL CODE’ and after that will indicate the time. To avoid the password selection after four running wrong typing the console blocks up next password entering for 30 sec (for 1 min after 5 typing, for 2 min after 6 typing and etc. After entering the legal password the blocking will be off.
  • Page 39: Partition Control At 'S2000-K' Keyboards

    S2000M MAINTENANCE GUIDE For example let the partition number 1200 named "Second v 1200: ARM FAILED floor" failed arming and the message "ARM FAILED" was displayed. To show failed zones press "TRBL" and choose the Second Flore state "ARM FAILED" by means of " 4 " or " 3 ".
  • Page 40 FIRE AND ALARM CONSOLE arming/disarming command is designated for all given device loops with group arming attribute. The common arming/disarming command is designated for all given device loops. Single loop arming Type password. ENTER CODE:_ Select ‘ARM’ menu item by ‘ 4 ’, ‘ 3 ’ and ‘ENT’ keys, or press v1 ARM hot key ‘1’.
  • Page 41: Device Alarm Reseting

    S2000M MAINTENANCE GUIDE Type password. ENTER CODE:_ Select ‘DISARM’ menu item by ‘ 4 ’, ‘ 3 ’ and ‘ENT’ keys, or v2 DISARM press hot key ‘2’. Select ‘DISARM GROUP’ menu item by ‘ 4 ’, ‘ 3 ’ and ‘ENT’...
  • Page 42: S2000-Aspt' Device Control

    FIRE AND ALARM CONSOLE 4- ‘OFF’ for a time given when the device relay output being configured; 5- blink; 6- blink; 7- blink. Initial state is ‘OFF’; 8- blink. Initial state is ‘ON’. Attention! The intrusion and fire alarm panelss ignore outputs control commands from the console, if they control the outputs itself (see intrusion and fire alarm panelss maintenance guides).
  • Page 43: Request For Loop State

    S2000M MAINTENANCE GUIDE detectors, or manual alarm call pointhas been activated,or manual launching command has been given. Select ‘LAUNCH’ for selecting launching command and press vLAUNCH ‘ENT’. CONFIRM LAUNCH Press ‘ENT’ to confirm launch and launching procedure will be DEVICE: 10 started.
  • Page 44: Console Date And Time Setting

    FIRE AND ALARM CONSOLE Type alarm loop number or select value by keys ‘ 4 ’, ‘ 3 ’ key and press ‘ENT’. If the command was successfully comleted ADC or measured value is displayed in format: v002/017: ‘ v device address / loop number: value’. In this example the measured by ADC value of loop №...
  • Page 45: Printing Event Buffer

    S2000M MAINTENANCE GUIDE Current time is displayed by LCD in HH:MM format (hours and TIME: HH:MM minutes). Enter new time. After changing time console forms two messages: ‘ ’ and ‘ ’. TIME CHANGED TIME STAMP Message ‘ ’ informs when user has changed time. Message ‘...
  • Page 46: Device And Console Programming Functions

    FIRE AND ALARM CONSOLE ENTER CODE:_ Type password. Select ‘SERVICE’ menu item by ‘ 4 ’, ‘ 3 ’ and ‘ENT’ keys, or v6 SERVICE press hot key ‘6’. Select ‘CANCEL ALARM’ menu item by ‘ 4 ’, ‘ 3 ’ and ‘ENT’ v65 CANCEL ALARM keys, or press hot key ‘5’.
  • Page 47: Rs-485 Device Address Changing

    S2000M MAINTENANCE GUIDE LCD displays current correction value (0 for our example). By SEC/DAY: 0 means of ‘ 4 ‘ and ‘ 3 ‘keys select new correction value and press ‘ENT’. Date setting Enter the programming menu (press button ‘PRG’).
  • Page 48: Console Extra Settings

    FIRE AND ALARM CONSOLE and connecting device with new address followed by state information. In case of operation faulting the console makes sound signal ‘Error’ and displays diagnostic message: ‘COMMAND ERROR: DEVICE OFF LINE’, ‘COMMAND ERROR: UNKNOWN COMMAND’, ‘COMMAND ERROR: ADDR UNKNOWN’ (2-wire device is not connected to ‘S2000-KDL’), ‘COMMAND ERROR: ADDR OCCUPIED’...
  • Page 49: Password Management

    S2000M MAINTENANCE GUIDE “ CODE LENGTH ” – maximum symbol number in user password (from 1 to 8). Password accepted automatically when it length is equal to given value. If the password is shorter then it needs to be finished by ‘ENT’ key pressing.
  • Page 50 FIRE AND ALARM CONSOLE adding new password or “CHANGE” for changing existing password. Type password and press “ENT”. Typing symbols will be NEW CODE: displayed as “*”.If signal “Error” has sounded it indicates after password typing it indicates that this password has already existed and if so enter another password.
  • Page 51: Console Address Setting In Prorgamming Mode

    2.2.4.8 Console RS-232 interface operative mode settings RS-232 outputs of ‘S2000M’ console (GND, DTR and TxD line) can be connected to printer or personal computer supplied with ‘ARM S2000’, ‘ARM Orion’ or ‘ARM Orion Pro’ software. Depending on connected to console equipment or software RS-232 interface mode...
  • Page 52: The Ring Rs-485 Interface Operative Mode Settings

    3) “ S2000 / PC ” – RS-232/RS-485 interface converter mode with auto switching in active mode (device operation mode) when personal computer fails. It is designed to reserve ‘ARM Orion’ operations by the ‘S2000M’ console. The default parameter value is “PRINTER”. To change parameter value make the following steps.
  • Page 53: Console Entering Into Programming Mode

    RS-485 line. The ends of RS-485 line are alternately connected to the console with the help of ‘S2000-SP1’ relay unit. Refer to the section “Technical support” on NVP ‘BOLID’ site www.bolid.ru additional information.
  • Page 54: Console Version Update

    98/2000/XP, connection cable for RS-232 interface, update program ‘ORION_PROG.exe’ and file with libraries for different ‘S2000M’ console versions (extention ‘chp’). Console connection to the computer for version update is shown on the Figure 5. Cable has to correspond shown on the picture type.
  • Page 55: Warranty

    Manufacturer warrants it ‘S2000M’ product to be in conformance with specification under normal transportation, storage, mounting and maintenance. Manufacturer warrants ‘S2000M’ product to be free from defects in materials and workmanship for 18 months since putting in to operation, but no more then 24 months since production under normal use and service.
  • Page 56: Appendix A 'S2000M' Console Dimensions

    FIRE AND ALARM CONSOLE Appendix A ‘S2000M’ console dimensions...
  • Page 57: Appendix B Zone Status List

    S2000M MAINTENANCE GUIDE Appendix B Zone status list Zone statuses are listed in priority decreasing order. If different zones of one partition have various statuses, the resulting status of the partition will be defined by the zone status of the highest priority.
  • Page 58 FIRE AND ALARM CONSOLE State Description Displayed "ENTRY ALARM" Entry zone alarm if entry delay has not elapsed ENTR ALARM "ENCLOSURE Device enclosure tamper detector has been broken TAM ALARM TAMPERING" "2-WIRE LINE Short circuit in "S2000-KDL" 2-wire addressable 2WRE SHORT SHORT CIRCUIT"...
  • Page 59 S2000M MAINTENANCE GUIDE State Description Displayed Zone is arming ( the arming command has been "ARMING DELAY" entered but the result of operation has not yet been ARMING... known) or arming delay is being counted Zone is normal armed for alarm loops or alarm addressable detectors, or zone is normal controlled "ZONE ARMED"...
  • Page 60 FIRE AND ALARM CONSOLE State Description Displayed "HIGH The pressure or water level has exceeded the EMERGENCY LV TOO HI emergency threshold ("Potok-3N") LEVEL" "LOW The pressure or water level is below the EMERGENCY LV TOO LOW emergency threshold ("Potok-3N") LEVEL"...
  • Page 61: Appendix С The List Of Messages Being Displayed

    S2000M MAINTENANCE GUIDE Appendix С The list of messages being displayed Event description Displayed event name Category The condition for launching of fire extinguishing equipment was met LAUNCHING DELAY and the launching delay is being counted The pulse for fire extinguishing equipment launching was given out...
  • Page 62 FIRE AND ALARM CONSOLE Event description Displayed event name Category Battery supply is out of range BATTERY FAILED Battery supply is restored BATTERY RESTORED AC power has been lost AC POWER FAILED AC power has been restored AC POWER RESTORE Device was restarted DEVICE RESTART The console has no response from the device through RS-485...
  • Page 63 S2000M MAINTENANCE GUIDE Event description Displayed event name Category The relay output load circuit has been restored RELAY RESTORE Addressable relay module fails to communicate to “S2000-KDL” or RELAY DISCONNECT “S2000-ASPT” devices Addressable relay module restored communication with “S2000-KDL” RELAY CONNECTED or “S2000-ASPT”...
  • Page 64 FIRE AND ALARM CONSOLE Event categories: 5 - ‘ZONE ARM/DISARM‘ 1 - ‘FIRES’ 6 - ‘ACCESS’ 2 - ‘ALARMS’ 7 - ‘RELAY’ 3 - ‘FAULTS’ 8 - ‘SYSTEM INFO’ 4 - ‘ARM/DISARM’ 9 - ‘AUXILIARY’...