supplied with №11 ("ASPT") and №33 ("ASPT-1") programs will be turned on with given
delay, but outputs supplied with №34 ("ASPT-A") and №35 ("ASPT-A1") programs will not be
turned on (in the last case will be turned on if control time restrictions are not given). There are
other distinctions between programs. Starting of relay outputs supplied with №34 and №35
programs is blocked up if there are blocking conditions in any associated partition. On the
contrary output supplied with №11 or №33 programs will be turned on if there is at least one
partition met the launching condition (specifically there are fire alarms and there are no broken
auxiliary alarm loop and failed outputs) without regard to another concerning partition states.
5) Executive programs №11 ("ASPT") and №34 ("ASPT-A") allow to turn output on
when either two smoke or heat detectors in partition have been activated or a manual fire
detector (IPR) has been started if the type "Manual launch" for IPR controlling zone was
configured.
6) Output 'FAULT' is used to control the operative status of fire partitions. Output
opening follows with:
short circuit, open circuit or fault of fire detector,
short or open circuit of output relay,
connection loss between the console and RS-485 lined control receiving device or relay
unit, or between 2-wire connected addressable detector or relay unit and "S2000-KDL"
controller,
short circuit or trouble of 2-wire addressable line,
primary or backup power supply troubles,
"Disarmed" or "Arming has failed" status of partition.
As this output is normalle closed the relay unit power down or open relay output circuit
are considered to be fault signals.
7) "Fire LAMP" output differs from "LAMP" by turning on only when all assigned
partitions are armed.
8) Program №17 ('Turn on for a given time before arming') can be used for 4-wired
detectors auto reset when arming. To do this the detectors are powered through normally closed
contact of 'S2000-SP1' device relay output. This output is given by the executive program №17
and control time sufficient to reset detectors. For 4-wired detectors alarm loops the arming delay
is to be given. Arming delay must be more then the sum of resetting time and maximum restore
time of detectors after power reset. As a result when arming command is given the relay will turn
on for given time with 4-wired power circuits being broken and thus reset activated detectors.
9) Programs № 38-45 can be used in gas, powder or aerosol fire extinguishing systems
based on "S2000M-ASPT" devices. These programs allow turning on or off device outputs both
for given time or as long as on/off condition is in effect. Controlling without time restrictions is
realized by givening the maximum control time value being egual to 8191,875 seconds.
Program № 38 "Turn on during launching delay" can be used for activating audible alarms and
light boxes "GET OUT!" and "KEEP OUT!" when launching delay.
Program № 39 also can be used in gas extinguishing system for several areas with the common
extinguishing installation with each area being protected with singular "S2000-ASPT" device.
"S2000-ASPT" devices control fire detector statuses and in case of fire generate launching
message and open gaseous discharge valve to protected area. The console can activate the fire
extinguishing system in "Launching" condition for any area giving out launching pulse to output
provided with executive program № 39 "Turn on during launching".
Program № 41 "Turn on if launching failed" can be used for launching of redundant fire
extinguishing installation.
1.2.23 Console allows assigning up to 32 entrance zones. Entrance zone represents alarm
loop with alarm delay ability. Alarm delay permit to enter the protected area through entrance
zone without immediate alarm and to disarm the premises. The delay factor can be given from 0
to 254 s. Entrance alarm loop being broken the console gets out the message 'ENTRY ALARM'.